[ VIII Test Run Mode ]
- 173 -
HWE0803A GB
Operation
Outdoor unit model
PURY-P168TSHMU-A
PURY-P96THMU-A PURY-P72THMU-A
Model name of BC controller CMB-P108NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/- [70°F/-]
Outdoor 8.3°C/6.1°C [47°F/43°F]
Indoor unit
No. of connected units
Unit
5
No. of units in operation 5
Model - 30/30/36/36/36
Piping
Main pipe
m
[ft]
5 [16-3/18"]
Branch pipe 10 [32-3/4"]
Total pipe length 55 [180-1/8"]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz]
38.5 [85]
Outdoor
unit
Electric current A 42.2
Voltage V 230
Compressor frequency Hz 71 48
LEV open-
ing
Indoor unit
Pulse
295/295/350/350
BC controller (1/2/3) 110/110/980
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.64/0.68
[382/98]
2.64/0.69
[382/335]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.60/2.27
[377/329]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
80 [176] 69 [156]
Heat exchanger outlet
(TH6)
0 [32] 0 [32]
Accumulator inlet -2 [28] 1 [34]
Accumulator outlet -3 [27] 1 [34]
Compressor inlet -3 [27] 1 [34]
Compressor shell bottom 40 [104] 40 [104]
Indoor unit
LEV inlet 34 [93]
Heat exchanger inlet 67 [153]