Mitsubishi Electronics PURY-P72 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 164 -
HWE0803A GB
Operation
Outdoor unit model
PURY-P120THMU-A
Model name of BC controller CMB-P104NU-G
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C
[80°F/67°F]
Outdoor
35°C/-
[95°F/-]
Indoor unit
No. of connected units
Unit
4
No. of units in operation 4
Model - 30/30/30/30
Piping
Main pipe
m
[ft]
5[16-3/8"]
Branch pipe 10 [32-3/4"]
Total pipe length 45 [147-5/8"]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz]
22.5 [50]
Outdoor
unit
Electric current A 29.5
Voltage V 230
Compressor frequency Hz 75
LEV open-
ing
Indoor unit
Pulse
230/230/230/230
BC controller (1/2/3) 2000/-/210
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.82/0.89
[409/129]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.73/2.72
[395/394]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
82 [180]
Heat exchanger outlet
(TH3)
43 [109]
Accumulator inlet 8 [46]
Accumulator outlet 8 [46]
Compressor inlet 20 [68]
Compressor shell bottom 42 [108]
Indoor unit
LEV inlet 22 [72]
Heat exchanger inlet 11 [52]