[ VII Control ]
- 137 -
HWE0803A GB
(3) Outdoor unit heat exchanger capacity control patterns
Model
Operation
mode
Operation
patterns
Solenoid valve
SV4a SV4b SV4c SV4d SV5c
P72 model Cooling-
only
Cooling-
main
1 OFF OFF - ON ON
2 OFF OFF - OFF ON
3 OFF ON - OFF ON
4 ON OFF - OFF ON
5ONON-OFFOFF
Heating-
only
1ONON-OFFOFF
Heating-
main
1 ON ON - ON OFF
2ONON-OFFOFF
Defrost 1 ON ON - OFF OFF
P96, P120 models Cooling-
only
Cooling-
main
1 OFF OFF OFF ON ON
2 OFF OFF OFF OFF ON
3 OFF OFF ON OFF ON
4 OFF ON ON OFF ON
5ONONONOFFOFF
Heating-
only
1ONONONOFFOFF
Heating-
main
1ONONONONOFF
2ONONONOFFOFF
Defrost 1 ON ON ON OFF OFF