Mitsubishi Electronics PURY-P72 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 165 -
HWE0803A GB
(2) Heating only operation
Operation
Outdoor unit model
PURY-P72THMU-A PURY-P96THMU-A
Model name of BC controller CMB-P104NU-G CMB-P104NU-G
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/-
[70°F/-]
21.1°C/-
[70°F/-]
Outdoor
8.3°C/6.1°C
[47°F/43°F]
8.3°C/6.1°C
[47°F/43°F]
Indoor unit
No. of connected units
Unit
32
No. of units in operation 3 2
Model - 24/24/24 48/48
Piping
Main pipe
m
[ft]
5 [16-3/8"] 5 [16-3/8"]
Branch pipe 10 [32-3/4"] 10 [32-3/4"]
Total pipe length 35 [114-13/16"] 25 [82]
Fan speed - Hi Hi
Amount of refrigerant
kg
[lbs-oz]
19.1 [42] 21.3 [47]
Outdoor
unit
Electric current A 16.8 24.1
Voltage V 230 230
Compressor frequency Hz 48 71
LEV open-
ing
Indoor unit
Pulse
205/203/200 406/406
BC controller (1/2/3) 110/-/520 110/-/590
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.61/0.69
[378/100]
2.67/0.68
[387/98]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.54/2.22
[368/321]
2.63/2.31
[381/335]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
69 [156] 80 [176]
Heat exchanger outlet
(TH6)
0 [32] 0 [32]
Accumulator inlet 1 [34] -2 [28]
Accumulator outlet 1 [34] -3 [27]
Compressor inlet 1 [34] -3 [27]
Compressor shell bottom 40 [104] 40 [104]
Indoor unit
LEV inlet 30[86] 38[100]
Heat exchanger inlet 63 [145] 70 [158]