Mitsubishi Electronics PUGH42AYB Heat Pump User Manual


 
036-21544-001 Rev. B (1103)
Mitsubishi Electronics 2003 17
PLH30AK+PUGH30 (Indoor Air = 1020 CFM)
75 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
Cooling
Capacity
(Btu/hr)
EER
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Pressures
(psig)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
63 29,544 10.17 2,905 17,275 20,651 25,522 30,393 33,769 57 203
65 30,285 10.26 2,952 15,472 18,848 23,428 28,008 31,384 58 204
67 31,025 10.35 2,999 13,670 17,046 21,334 25,623 28,999 59 205
69 31,766 10.43 3,045 11,867 15,243 19,241 23,238 26,615 60 206
71 32,506 10.52 3,090 10,065 13,441 17,147 20,854 24,230 61 207
85 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
Cooling
Capacity
(Btu/hr)
EER
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Pressures
(psig)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
63 28,669 9.21 3,114 16,945 20,321 24,624 28,927 32,303 62 234
65 29,518 9.38 3,146 15,244 18,620 22,949 26,929 30,305 65 238
67 29,413 9.58 3,070 13,543 16,919 21,273 24,931 28,307 67 242
69 30,738 9.64 3,187 11,841 15,218 19,250 22,934 26,310 69 242
71 32,063 9.71 3,303 10,140 13,516 17,226 20,936 24,312 70 242
95 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
Cooling
Capacity
(Btu/hr)
EER
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Pressures
(psig)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
63 27,794 8.36 3,323 16,616 19,992 23,726 27,461 30,837 66 265
65 28,750 8.61 3,340 15,016 18,392 22,469 25,850 29,226 71 272
67 27,800 8.85 3,141 13,416 16,792 21,212 24,239 27,615 76 279
69 29,709 8.92 3,330 11,816 15,192 19,258 22,629 26,005 77 279
71 31,619 8.99 3,516 10,216 13,592 17,305 21,018 24,394 79 278
105 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
Cooling
Capacity
(Btu/hr)
EER
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Pressures
(psig)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
63 25,422 7.33 3,468 15,646 19,022 22,630 26,238 29,614 69 299
65 26,616 7.55 3,524 14,075 17,451 21,290 24,781 28,157 72 304
67 26,856 7.74 3,469 12,504 15,880 19,950 23,323 26,699 76 308
69 28,526 7.91 3,605 10,932 14,309 18,261 21,866 25,242 78 310
71 30,196 8.08 3,737 9,361 12,737 16,573 20,408 23,784 80 311
115 °F Outdoor Air Temperature
Indoor Wet
Bulb (°F)
Cooling
Capacity
(Btu/hr)
EER
Total
Power
(Watts)
Net Sensible Cooling Capacity (Btu/hr)
Pressures
(psig)
Indoor Dry Bulb (°F)
70 75 80 85 90 Suction Discharge
63 23,051 6.38 3,613 14,676 18,052 21,534 25,016 28,392 72 332
65 24,481 6.60 3,708 13,134 16,510 20,111 23,712 27,088 74 335
67 25,912 6.82 3,797 11,591 14,967 18,687 22,407 25,783 76 338
69 27,342 7.05 3,880 10,049 13,425 17,264 21,103 24,479 78 341
71 28,773 7.27 3,958 8,507 11,883 15,841 19,799 23,175 80 343
PERFORMANCE DATA - OPERATING PRESSURES - COOLING
4