Mitsubishi Electronics PAC-YG60MCA Air Conditioner User Manual


 
8
7-3. Connecting the Signal Lines
Separately procure items such as terminal blocks and cables locally.
The maximum wire length is 100 m. However, since the use of long wires makes the device susceptible to
noise, using wires shorter than 10 m is recommended.
(1) Pulse input (non-voltage a contact)
* To use these, various settings need to be configured. Refer to "8 Initial Setting Procedure".
Ch1 Ch3
C
N 1
0
/
11
/
1
9
/
2
0
Ch2 Ch4
++++
Note:
The pulse weight can be added to each of the inputs of
channels 1 to 4.
For details, refer to "9 Switch List".
This device does not support level meters.
To use a level meter, incorporate a Converter circuit
externally and convert to pulse input.
Caution:
The polarity of the input terminals is important, so be sure to
match the polarity when using contacts that have polarity.
Select a contact with a minimum applicable load of 1 mA or
less.
Supply 24 VDC 1 mA from the positive terminal to the
contacts of the meters.
The pulse unit of the watt-hour meter being used should be
1 kWh/pulse or less. Note that the apportioning error will
increase if a watt-hour meter with large pulse unit is used.
Strip 12±1 mm (15/32 ±1/32 in) of the wire coating and insert
firmly into the terminal.
Make sure that the copper wiring is not short-circuiting the
plates (cover, lower case) or neighboring wires.
Perform wiring so that the terminal block is not strained.
If strained, use a wire guide or junction terminal to alleviate
the stress on the terminal block.
Watthour
meter
Water
meter
Gas
meter
Calorimeter
Line
Onsite
Example:
24 VDC