Mitsubishi Electronics PAC-YG60MCA Air Conditioner User Manual


 
10
Set the dip switches for function selection according to the system to be used.
At the time of shipment, all dip switches are set to OFF and the M-NET address is set to 01.
*1: When using a system controller (G(B)-50A or TG-2000A), select the "SC setting" and set the pulse weight value settings from a system controller. If set
to another setting, this dip switch setting is prioritized even when set from a system controller.
*2: The pulse unit of the watt-hour meter being used should be 1 kWh/pulse or less. Note that the apportioning error will increase if a watt-hour meter with
large pulse unit is used.
9 Switch List
SW
Supported
Channel
Function OFF ON Remark
SW01 1 Channel 1 Use of input contact No Yes Set whether to use the Channel 1 input.
2 Channel 2 Use of input contact No Yes Set whether to use the Channel 2 input.
3 Channel 3 Use of input contact No Yes Set whether to use the Channel 3 input.
4 Channel 4 Use of input contact No Yes Set whether to use the Channel 4 input.
5 Unused Set to OFF
6 Unused Set to OFF
7 Unused Set to OFF
8 Unused Set to OFF
SW02
1
Channel 1
Pulse weight value setting:
SC setting (*1):
× 0.1:
× 1:
× 10:
SW02-1,
OFF
OFF
ON
ON
SW02-2
OFF
ON
OFF
ON
Set 1 pulse of the meter connected to channel 1.
2
3
Channel 2
Pulse weight value setting:
SC setting (*1):
× 0.1:
× 1:
× 10:
SW02-3,
OFF
OFF
ON
ON
SW02-4
OFF
ON
OFF
ON
Set 1 pulse of the meter connected to channel 2.
4
5
Channel 3
Pulse weight value setting:
SC setting (*1):
× 0.1:
× 1:
× 10:
SW02-5,
OFF
OFF
ON
ON
SW02-6
OFF
ON
OFF
ON
Set 1 pulse of the meter connected to channel 3.
6
7
Channel 4
Pulse weight value setting:
SC setting (*1):
× 0.1:
× 1:
× 10:
SW02-7,
OFF
OFF
ON
ON
SW02-8
OFF
ON
OFF
ON
Set 1 pulse of the meter connected to channel 4.
8
SW03 1 Unused Set to OFF
2 Unused Set to OFF
3 Unused Set to OFF
4 Unused Set to OFF
5 Unused Set to OFF
6 Unused Set to OFF
7 Unused Set to OFF
8 Unused Set to OFF
SW06
M-NET address
(Address 10s) 0 to 9 (decimal)
An address from 01 to 50 can be set.
Set an address that is not the same as that of
another unit.
SW07 (Address 1s) 0 to 9 (decimal)
SW08
1
Communication error status display (error code
display)
Temporary mask setting
Change the switch to ON once
and then return it to OFF.
Only enabled during communication error status
display.
* The communication error status display is
masked for 10 seconds and the contact input
status is displayed.
2 Unused Set to OFF
3 Unused Set to OFF
4 Unused Set to OFF
5 Unused Set to OFF
6 Unused Set to OFF
SW09 1 Unused Set to OFF
2 Unused Set to OFF