Mitsubishi Electronics PAC-YG60MCA Air Conditioner User Manual


 
5
6-2. Installation Procedure
The PI controller PAC-YG60MCA does not have a waterproof structure.
Be sure to install the PI controller inside a control panel that is located indoors.
Prepare a control panel capable of storing this device such as the one shown in the figure. (Install the device in a control
panel strong enough to withstand a weight of 0.6 kg [1
3
/8 lb].)
This device can be installed flat or vertically. Clear the space shown below when installing.
(1) Fix the top of this unit to the control panel at two points by loosely tightening the screws (M4) that were procured locally.
Fix the bottom in place with two screws and then tighten all four of the screws.
(2) To remove the cover, as shown in the figure, remove the two screws for fixing the cover in place and then remove the cover by
unhooking the upper hook section from the lower case. To attach the cover, hook the upper hook section on the lower case and then
fix the cover in place with the two screws that were removed.
Note: The space shown above does not include space for peripherals. Additionally, the amount of space necessary varies according to
the functions that are used and the wiring method. Secure enough space appropriate for the type of installation.
Note: Two hooks are located on the upper section of the cover.
100
(
3
15
/
16
)
100
(
3
15
/
16
)
100
(
3
15
/
16
)
100
(
3
15
/
16
)
Size of the device: 200 (W) × 120 (H) × 45 (D) mm/
7
7
/8 (W) × 4
3
/4 (H) × 1
25
/32 (D) in
Unit: mm (in)
110
(
4
11
/
32
)
150
(
5
29
/
32
)
Screw pitch
Unit: mm (in)
Hooks
Screws for fixing
the cover