Mitsubishi Electronics PAC-YG60MCA Air Conditioner User Manual


 
3
5 Example of System Configuration
Note:
For the shield ground of the M-NET centralized control line for central control, use single-point grounding at the power unit for
the transmission line.
However, when supplying electric power to the M-NET centralized control line from the R410A series outdoor unit without using
a power supply unit for the transmission line, use single-point grounding at the TB7 of that outdoor unit.
Furthermore, when connecting this device to the M-NET indoor control line, use grounding at the TB3 for each outdoor unit
system.
Connecting an Uninterruptible power supply (UPS) to the 24 VDC power supply is recommended in order to prevent the loss of
pulse data in the event of a power failure.
If a UPS cannot be connected, try to make the AC power supply to the 24 VDC power supply as much same as the power supply
line to the meters.
This device does not support level meters. To use a level meter, incorporate a Converter circuit externally and convert to pulse
input.
If this device is connected to an M-NET indoor control line and the outdoor unit is down because, for example, the power supply
is interrupted for servicing or there is a failure, the PI controller cannot be controlled from the system controller.
TB3
M-NETM-NET
LAN
TB7
Centralized control line
Indoor control line
PI controller
G-50A or GB-50A
G(B)-50A Web
or TG-2000A
Uninterruptible
power supply
(UPS)
Watt-hour meter with
pulse transmitter, etc.
<Restrictions>
Maximum of 5 units (total of 20 channels) per G(B)-50A
However, the number of units that can be connected to a
G(B)-50A is up to 50 including this device, an indoor unit,
Lossnay unit, etc.
* For the number of units that can be connected when
controlling this device with TG-2000A, refer to the
instruction manual for TG-2000A.
* This figure omits the power supply line and only shows the transmission line.
Power supply unit
PAC-SC50KUA
PI controller
24 VDC
power supply
Up to 4 contacts
Watt-hour meter with
pulse transmitter, etc.
Uninterruptible
power supply
(UPS)
24 VDC
power supply
Up to 4 contacts
City Multi