Mitsubishi Electronics MSZ-FA35VA Air Conditioner User Manual


 
28
Check of auto front panel
H
Is the connector of the front panel
driving motor unit or the indoor
electric control P.C. board unplugged?
Front panel is normal.
Replace the front panel
driving motor unit.
Does the front panel automatically
open? (Does it start to move?)
Yes
Is the front panel held 10mm or
more upper than the level line of
the nozzle top?
Yes
No
Turn the remote controller ON.
Plug in the connector and
check from the start again.
Is the resistance value between
terminals of the front panel driving
motor unit normal?
Replace the indoor electric
control P.C. board.
Replace the front panel
driving motor unit.
No
No
Yes
Yes
No
Indoor unit and outdoor unit do not operate.
10 mm or
more
Z-Z side view
OB371_--1qxp 05.1.17 12:50 Page 28