Mitsubishi Electronics 10 Air Conditioner User Manual


 
- 50 -
[PRODUCT]
ROOFTOP PACKAGE AIR COOLED HEATPUMP AND COOLING ONLY UNITS
Product type
PRH SERIES
Product number : Heat pump
PRH-5YA PRH-8YA PRH-10YA PRH-15YA PRH-20YA
[INDOOR AIR CIRCUIT]
Number of blowers
12222
Diameter of blowers
mm
253 393
Width of blowers
mm
182 282
Blower drive
Belt drive
Fan motor output
kW
0.75 1.1 1.5 2.2 3.0
Normal fan motor run current
A
2.26 2.90 3.28 4.72 6.06
Air quantity
L/s
900 1,400 1,660 2,800 3,160
External static pressure
Pa
100 200
Supply air dimensions (h
w)
mm
mm
300850 300 1,150 428 1,820
Return air dimensions (h
w)
mm
mm
410900 410 1,200 464 1,879
[CONDENSER]
Quantity
11122
Face area
sq.m
1.3 1.12 1.46 21.07 21.32
Rows deep
33333
Rows high
30 23 30 30 37
Finned length
mm
1,700 1,920 21,400
Face velocity
m/s
1.2 2.8 2.1 2.9 2.3
Fins per meter
473 473 473 473 473
Fin material thickness
mm
0.12
Fin material
Aluminium
Fins pitch
mm
2.11 2.11 2.11 2.11 2.11
Tube diameter
mm
9.52
Gauge of copper
tube mm
0.35
Number of circuits
11 11 15 11 14
[OUTDOOR AIR CIRCUIT]
Number of fans
11122
Diameter of fans
mm
600 800
Pitch of fans
mm
--- 990
Fan drive
Direct drive
Fan motor output
kw
0.15 0.35 0.35 20.35 20.35
Quantity
11122
Normal fan motor run current
Amps
0.6 1.3 1.3 21.3 21.3
Fan motor speed
rpm
650 645
Air quantity
L/s
1,583 3,083 23,083
[ENCLOSURE AND FRAME]
height
mm
1,000 1,200
Dimension width
mm
1,000 1,300 1,990
depth
mm
1,600 1,840
Color
Munsell 5Y8/1
Panel thickness
mm
1.2
Condensate drain size
mm
25.4
Weight
kg
299 393 413 698 729
Sound power level
dbA
73 75 75 79 79
Sound pressure level
dbA
62 64 64 68 68