Mercury PR0091 Thermostat User Manual


 
Mercur
y
6-5 Stat
Installation & User Guide
Parameter Tables:
Parameter table for 5 Channel Thermostat
Ensure that all power is
Number Parameter Range
o
C (
o
F ) Step Units Default
P-01 Stat1 Temp Cut-In -49 to 30
o
C (-56.2 to 86) 0.1 Deg 15.0
P-02 Stat1 Diff 0 to 10
o
C (32 to 50) 0.1 Deg 5.0
P-03 Stat1 Select 0 = Off
1 = Timer
2 = Probe 1
3 = Probe 2
4 = Probe 3
5 = Probe 4
6 = Probe 5
1 2
P-04 Stat1 Type 0 = Cooling
1 = Heating
1 1
P-06 Stat1 Frost Detect -42 to 128
o
C (-43 to 262) 0.1 Deg 0.0
P-07 Stat1 High Temp Alarm -42 to 128
o
C (-43 to 262) 0.1 Deg 25.0
P-08 Stat1 Low Temp Alarm -42 to 128
o
C (-43 to 262) 0.1 Deg 0.0
P-09 Stat1 Alm Delay 00:00 to 99:00 01:00 mm:ss 20:00
P-10 Stat1 Rly Inv 0 = Off
1 = On
1 0
P-11 Stat2 Temp Cut-In -49 to 30
o
C (-56.2 to 86) 0.1 Deg 15.0
P-12 Stat2 Diff 0 to 10
o
C (32 to 50) 0.1 Deg 5.0
P-13 Stat2 Select 0 = Off
1 = Timer
2 = Probe 1
3 = Probe 2
4 = Probe 3
5 = Probe 4
6 = Probe 5
1 3
P-14 Stat2 Type 0 = Cooling
1 = Heating
1 1
P-16 Stat2 Frost Detect -42 to 128
o
C (-43 to 262) 0.1 Deg 0.0
P-17 Stat2 High Temp Alarm -42 to 128
o
C (-43 to 262) 0.1 Deg 25.0
P-18 Stat2 Low Temp Alarm -42 to 128
o
C (-43 to 262) 0.1 Deg 0.0
P-19 Stat2 Alm Delay 00:00 to 99:00 01:00 mm:ss 20:00
P-20 Stat2 Rly Inv 0 = Off
1 = On
1 0
P-21 Stat3 Temp Cut-In -49 to 30
o
C (-56.2 to 86) 0.1 Deg 15.0
P-22 Stat3 Diff 0 to 10
o
C (32 to 50) 0.1 Deg 5.0
P-23 Stat3 Select 0 = Off
1 = Timer
2 = Probe 1
3 = Probe 2
4 = Probe 3
5 = Probe 4
6 = Probe 5
1 4
P-24 Stat3 Type 0 = Cooling
1 = Heating
1 1
P-26 Stat3 Frost Detect -42 to 128
o
C (-43 to 262) 0.1 Deg 0.0
P-27 Stat3 High Temp Alarm -42 to 128
o
C (-43 to 262) 0.1 Deg 25.0
P-28 Stat3 Low Temp Alarm -42 to 128
o
C (-43 to 262) 0.1 Deg 0.0
P-29 Stat3 Alm Delay 00:00 to 99:00 01:00 mm:ss 20:00
P-30 Stat3 Rly Inv 0 = Off
1 = On
1 0
switched off before
installing or maintaining
this product
Revision 1.2 Page 7 of 21