6.3 Reconditioning and maintenance
Parts of the system that have a fault are not able to perform their functions efficiently or at all. There-
fore have faults repaired as soon as possible by a qualified and authorized company, preferably the one
that performs the periodic maintenance of your system.
Fire detection systems have to be serviced and - if necessary - reconditioned periodically by a qualified
maintainer. Only specialized companies that are demonstrably periodically trained specifically for the
functions of this specific fire detection system by LST or by persons being explicitly authorized by
LST.
A fire detection system that has not been serviced at all or not competently may not be able to
fulfill its purpose to detect a fire reliably and fast. Aside from the resulting gross negligence dan-
ger to human life and to property, a fire insurance may reject the claim for compensation in
such cases!
6.4 Specifications of control panel devices of Series BC216
Mains voltage 230VAC +10/-15%, 50Hz
Power requirement 60VA
Supply current max. 0.26A
Output-/rated voltage typ. 28VDC
Peak current max. 1.8A
Case steel sheet, 1mm, powder coated
Colour grey-white, RAL9002
Dimensions w × h × d 420 × 520 × 120 (mm)
Weight without battery ca. 6kg
Ambient temperature -5°C to +50°C
Relative humidity of air 95% (not condensed)
Further detailed specifications are available in Part B of the User Manual of the fire detection control
panel Series BC216.