Lochinvar 400 - 801 Boiler User Manual


 
1 Service (continued)
Service Manual
17
Menu
Sub
Item
Description
See
Page
User Access Installer Access
Display Modify Display Modify
F
18 Boost Temperature 23 No No Yes Yes
19 Boost Time 23 No No Yes Yes
G
1 Anti-Cycling Time 23 No No Yes Yes
2 Anti-Cycling Override Differential 23 No No Yes Yes
3 Ramp Delay (Enable, Disable) 23 No No Yes Yes
4 SH Ramp Delay 24 No No Yes Yes
H
1 Controlling Sensor 24 No No Yes Yes
2 BMS Tstat Input (Active/Inactive) 24 No No Yes Yes
3 BMS (Active/Inactive) 24 No No Yes Yes
4 ModBus (Active/Inactive) 25 No No Yes Yes
5 ModBus T/O (Timeout) 25 No No Yes Yes
6 Cascade Address 25 No No Yes Yes
7 Cascade Type (L/L / EFF) 25 No No Yes Yes
8 Max Cascade Outlet Set Point 25 No No Yes Yes
9 Cascade Offset 25 No No Yes Yes
10 Cascade Off/On Differential 25 No No Yes Yes
11 Min On/Off Time 25 No No Yes Yes
12 Min Next On Time 25 No No Yes Yes
13 Boiler Size 25 No No Yes Yes
I
1 System Pump Delay 26 No No Yes Yes
2 Boiler Pump Delay 26 No No Yes Yes
3 DHW Pump Delay 26 No No Yes Yes
4 Boiler Pump Anti-Seize Delay 26 No No Yes Yes
5 Boiler Pump Min Voltage 26 No No Yes Yes
6 System Pump Type (CFH/WWSD) 26 No No Yes Yes
7 DHW Pump Anti-Seize Delay 26 No No Yes Yes
8 System Pump Anti-Seize Delay 26 No No Yes Yes
Parameter table
Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where
to access them
CONTROL MODES
OUTDOOR
RESET
ANTI-CYCLING
CIRCULATION PUMPS