3 Troubleshooting (continued)
39
Service Manual
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Flame
Sequence
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the SMART
SYSTEM display to
reset.)
The flame detector circuit is seeing a flame
signal while no flame is present.
• Check supply voltage for proper polarity.
• Check external wiring for voltage feedback.
• Check the flame rod and make sure it is clean.
• Check the internal wiring for bad connections.
• Replace main control board.
Auto Reset
High Limit
The outlet water temperature has exceeded
the setting of the automatic reset high limit.
Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the boiler is piped properly into the heating
system. Refer to Section 6 - Hydronic Piping of the
Knight XL Installation and Operation Manual
for the proper piping methods for the Knight XL boiler.
Check 120 vac to boiler pump motor on a call for
heat. If voltage is not present, check wiring back to
the main control board.
Replace the main control board if necessary.
• If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
If the system pump is a variable speed pump, ensure
that the system flow is not less than the boiler flow.
If operating on something other than an outlet sensor,
check temperature setting of the main control board.
If the optional manual reset high limit has tripped,
check setting of the device.
Check resistance of water sensors and compare to
Table 3-2A on page 35 of this manual. Replace
sensor if necessary.
Replace high limit.
Fan Low
OR
Fan Speed Low
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the SMART
SYSTEM display to
reset.)
The actual fan RPM is 30% lower than what
is being called for.
Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 3 - General Venting of the
Knight XL Installation and Operation Manual for
proper lengths.
Check for obstruction or blockage in the vent/air
intake pipes or at terminations.
Check the wiring connections at the fan and at the
main control board.
Replace the fan.
Replace the main control board.
Blown fuse.
Replace fuse F2 on the control board, see page 33
of this manual.