Lochinvar 000 Boiler User Manual


 
51
OPERATION/DIAGNOSTIC
LIGHTS, RESETS AND SWITCHES
ADJ
HI-LIMIT
CIRCUIT
BREAKER
ALARM
RESET
SOUND
ALARM
POWER
SILENCE
AUTO
RESET TEST
MANUAL
LOW WATER CUT-OFF
ALARM
BURNER
FIG. 67 Burner Assembly
FIG. 66 Exterior Control Panel
The control panel has a lighted ON/OFF power switch and 11
indicating lights and switches to show operation, control sensed
malfunctions and diagnostics.
TABLE - AA
Diagnostic Lights and Switches
Indicator Function
Power Lighted ON/OFF Main Power Switch.
_________________________________________________________________________________________________________
Alarm Silence Rocker Switch to Silence an Optional Audible Alarm.
_________________________________________________________________________________________________________
Alarm Light Amber Indicating Light for an Alarm Condition.
_________________________________________________________________________________________________________
High Limit Light Red Indicating Light for Water Temperature Exceeding Maximum Setting of High Limit Control.
_________________________________________________________________________________________________________
High Limit Knob Adjustable Rotary Knob to Set Maximum Water Temperature.
_________________________________________________________________________________________________________
High Limit Reset Red Push Button to Reset High Limit when High Limit Setting is Exceeded.
_________________________________________________________________________________________________________
Circuit Breaker Reset Button for a 5 Amp breaker on the 24 VAC Control Circuit.
_________________________________________________________________________________________________________
Low Water Cut-Off
_________________________________________________________________________________________________________
Test Switch Black Momentary Rocker Switch interrupts the sensing circuit of the Low Water Cut-Off to prove
operation.
_________________________________________________________________________________________________________
Reset Switch Red Momentary Rocker Switch to Reset the Low Water Cut-Off after a test or Low Water Condition
when operating in the Manual Reset Mode.
_________________________________________________________________________________________________________
Command Display
_________________________________________________________________________________________________________
Run/Stop Switch “RUN” allows normal operation - “STOP” shuts down operation, but allows communication with a
network.
_________________________________________________________________________________________________________
Ignition Control
_________________________________________________________________________________________________________
Flame Failure Reset Red Push Button to reset the Hot Surface Ignition Control when a hard lockout condition from a Flame
Failure has occurred.