BIASI B/40
PAGE 10
Good, reliable operation with a minimum of service starts with attention to the small details:
1. Setting the nozzle position and electrodes "by the book" using the manufacturer's gauges.
2. Installing a quality micron filter at the burner.
3. Making careful/tight flare connections without couplings on oil suction line.
4. Checking fuel pump pressure.
5. Checking draft at the breeching to insure it is adequate to overcome flue gas resistance.
6. Setting the air band properly with well maintained instruments. A good target is 11% to 12.5% of (CO
2
) or 6.5%
to 3.8% of (O
2
).
Note: Oil and Gas burners on B40-series boilers cannot be properly commissioned
without instruments and gauges.
The following information applies only to the BIASI B-40 series boilers at a maximum output
for power venters or lined chimneys only.
8. Burner Setup:
BURNER MANUFACTURER Heatwise
Boiler Model B-406 B-407 B-408 B-409 B-410 B-411 B-412
Burner Model
P2-KA P2-K P2-K DE-10 DE-10 DE-10 DE-10
Firing Rate
2.2 GPH 2.8 GPH 3.5 GPH 4.25 GPH 5.0 GPH 5.7 GPH 6.4 GPH
Insertion Depth
FULL FULL FULL FULL FULL FULL FULL
Nozzle
2.00 X 45 2.25 X 60 2.75 X 60 3.25 X 60 3.75 X 60 4.5 X 45 5.50 X 45
Spray Pattern
solid solid solid solid solid solid solid
Pump Pressure
140 psi 170 psi 175 psi 175 psi 175 psi 160 psi 140 psi
Head Position
12 16 18 1 1.5 2 2.5
Air Setting
11.50 15.00 18.00 3.5 4.5 5.5 6.75
BURNER MANUFACTURER Riello
Boiler Model B-406 B-407 B-408 B-409 B-410 B-411 B-412
Burner Model
F-10 F-10 F-15 F-15 F-15 F-20 F-20
Firing Rate
2.4 GPH 2.6 GPH 3.3 GPH 4.0 GPH 4.6 GPH 5.3 GPH 5.9 GPH
Insertion Depth
4.5" 4.5" 4.5" 4.5" 4.5" 4.5" 4.5"
Nozzle
2.00X60 2.00X60 2.50X60 3.00X60 3.50X60 4.0X60 4.5X60
Spray Pattern
B B B B B B B
Pump Pressure
145 PSI 175 PSI 175 PSI 175 PSI 175 PSI 175 PSI 175 PSI
Turbulator
3.75 4.5 1.8 2.1 2.8 3.1 5
Air Gate
5 6 3 4 5.5 4 6
BURNER MANUFACTURER Beckett
Boiler Model B-407 B-407 B-408 B-409 B-410 B-411 B-412
Burner Model CF 375
CF 375 CF 500 CF 500 CF 800 CF 800 CF 800
Firing Rate
2.1 GPH 2.7 GPH 3.2 GPH 3.7 GPH 4.3 GPH 4.8 GPH 5.3 GPH
Insertion Depth
4.5" 4.5" 4.5" 4.5" 4.5" 4.5" 4.5"
Nozzle
1.75X60 2.00X45 2.75X45 2.75X45 3.25X45 4.0X30 4.0X30
Spray Pattern
ES hollow solid solid solid solid solid
Pump Pressure
140 psi 180 psi 140 psi 180 psi 175 psi 145 psi 180 psi
Head Type
Head Position
0 2 3 4.5 3 3 4.5
Air Setting
9/0 3/1 7/0 10/0 7/0 8/0 10/2