Liebert 8 Tons Humidifier User Manual


 
Microprocessor Control
42
3.18 Run Diagnostics
By selecting Run Diagnostics, maintenance personnel can check system inputs, outputs, and conduct
a test of the microcontroller circuit board from the wall box control. A review of the system inputs and
the microcontroller test can be done without interrupting normal operation.
Test Outputs
When this feature is selected, the controller is effectively turned off. When stepping from one load
to the next, the previous load is automatically turned off. The loads can also be toggled on/off by
selecting “ENTER”. Once turned on, the output will remain on for five minutes unless toggled off
or the test outputs function is exited by selecting “MENU/ESC” (Compressor is limited to 15 sec-
onds on to prevent damage.
The outputs are:
•Main Fan
Compr1 (3-ton)
Compr1 & HGBP1
Compr2
Compr2 & HGBP2
Compr1 & Compr2
Chill Water/Gly (if present)
Reheat 1
Reheat 2
SCR Reheats (if present)
Humidifier
Common Alarm
Test Inputs
With the unit on and the fan running, the input states may be displayed for the following devices:
•Input Power
High Water in Pan
High Head Comp1
High Head Comp2
Air Sail Switch (requires additional factory-installed components)
•Filter Clog
Humidifier Prob.
Custom Alarm #1
Custom Alarm #2
Custom Alarm #3
!
CAUTION
Testing compressor output for more than a few seconds could damage the compressor. To
eliminate damaging the compressor during testing, DO NOT test compressor output for more
than a few seconds.
!
CAUTION
Extended unit operation in the test outputs mode for troubleshooting may cause damage to
unit. DO NOT operate unit in the test outputs mode any longer than is necessary for
troubleshooting.
NOTE
Fan turned on with all loads.