Lennox International Inc. Gas Units Gas Heater User Manual


 
Page 17
Use PVC primer and solvent cement or ABS solvent cement
meeting ASTM specifications, refer to Table 4. As an alter-
nate, use all purpose cement, to bond ABS, PVC, or CPVC
pipe when using fittings and pipe made of the same materi-
als. Use transition solvent cement when bonding ABS to ei-
ther PVC or CPVC.
Low temperature solvent cement is recommended. Metal or
plastic strapping may be used for vent pipe hangers. Uni-
formly apply a liberal coat of PVC primer for PVC or use a
clean dry cloth for ABS to clean inside socket surface of fit-
ting and male end of pipe to depth of fitting socket.
Canadian Applications Only − Pipe, fittings, primer
and solvent cement used to vent (exhaust) this ap-
pliance must be certified to ULC S636 and supplied by a
single manufacturer as part of an approved vent (ex-
haust) system. When bonding the vent system to the fur-
nace, use ULC S636 approved One−Step Transition Ce-
ment to bond the pipe to the flue collar, or to bond the 90°
elbow or reducing 90° elbow to the flue collar. In addi-
tion, the first three feet of vent pipe from the furnace flue
collar must be accessible for inspection.
Table 5 lists the available exhaust termination kits, as well
as vent pipe equivalencies which must be used when siz-
ing vent pipe. All Lennox vent terminations are PVC.
TABLE 5
OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES
UNIT
MODEL
VENT
PIPE
DIA.
(in.)
Vent Pipe Length Equivalency (feet)
Outdoor Ex-
haust Accel-
erator
(Dia. X
Length)
Outdoor Ex-
haust Accel-
erator
(Dia. X
Length)
1−1/2"
Concentric
Kit
2" Con-
centric Kit
3" Con-
centric Kit
2" Wall Plate
Kit
3" Wall Plate
Kit
2" Wall
Ring Kit
1−1/2" X 12"
2" X 12"
71M80
or 44W92
69M29
or 44W92
60L46
or 44W93
22G44
or 30G28
44J40
or 81J20
15F74
36B−045
2 4
Not
Allowed
12
Not
Allowed
Not
Allowed
4 4* 4
2−1/2 5
Not
Allowed
15
Not
Allowed
Not
Allowed
5 5* 5
3 7
Not
Allowed
21
Not
Allowed
Not
Allowed
7 7* 7
4 14
Not
Allowed
42
Not
Allowed
Not
Allowed
14 14* 14
36B−070
36B−071
2 4
Not
Allowed
12
Not
Allowed
Not
Allowed
4 4* 4
2−1/2 5
Not
Allowed
15
Not
Allowed
Not
Allowed
5 5* 5
3 8
Not
Allowed
24
Not
Allowed
Not
Allowed
8 8* 8
4 14
Not
Allowed
42
Not
Allowed
Not
Allowed
14 14* 14
48C−090
60C−090
60C−091
2
Not
Allowed
1
Not
Allowed
3 3
Not
Allowed
1 1**
2−1/2
Not
Allowed
2
Not
Allowed
6 6
Not
Allowed
2 2**
3
Not
Allowed
2
Not
Allowed
6 6
Not
Allowed
2 2**
4
Not
Allowed
4
Not
Allowed
12 12
Not
Allowed
4 4**
48C−110
60C−110
60C−111
2−1/2
Not
Allowed
2
Not
Allowed
6 6
Not
Allowed
2 2
3
Not
Allowed
2
Not
Allowed
6 6
Not
Allowed
2 2
4
Not
Allowed
4
Not
Allowed
12 12
Not
Allowed
4 4
60D−135
3
Not
Allowed
6
Not
Allowed
Not
Allowed
15
Not
Allowed
6
Not
Allowed
4
Not
Allowed
10
Not
Allowed
Not
Allowed
25
Not
Allowed
10
Not
Allowed
*Requires field−provided and installed 1−1/2" exhaust accelerator.
**Requires field−provided and installed 2" exhaust accelerator.
 Termination kits 44W92 (includes 1−1/2" reducer), 44W93,
30G28 and 81J20 approved for use in Canadian installations.