Jotul F 100 USA Fan User Manual


 
9
Prefabricated Chimneys
When connecting the Jøtul F 100 USA to a prefabricated
metal chimney always follow the pipe manufacturer’s
instructions and be sure to use the components that are
required. This usually includes a “smoke pipe adapter”
that is secured to the bottom section of the metal chimney
and allows the chimney pipe to be secured to it with two
sheet metal screws. See figure 8.
Clearance to Combustibles
Floor Protection
The Jøtul F 100 USA requires one of the following forms
of hearth protection:
1. Any UL, ULC or WH listed hearth board. (No bottom
heat shield required).
2. Any noncombustible material with use of the bottom
heat shield.
All forms of protection must include a noncombustible
surface extending forward from the glass panel at least
16” for the U.S., or 18” (46cm) for Canada. Protection
must extend 8” (21 cm) from the sides and rear for both:
the U.S. and Canada.
This will result in a minimum floor protection of 37” W x
38” D for the U.S. or 37” W x 40” D for Canada. See
figure 9.
In a rear vent installation, the floor protection must also
extend under the stove pipe a minimum of 2” (5 cm)
beyond either side of the pipe. See figure 9.
Figure 8. Prefabricated Listed Type HT Chimney.
Listed
Ceiling
to
Storm
Listed Cap
Combustible
Floor
Specified
Attic
Insulation
Flashing
Chimney
Figure 9. Hearth Protection.
A: 8” (21 cm)
B: 16” (US)
B: 46 cm (Can)
2”(5 cm)
37”U.S & CAN
B
A
A
A
38” (97 cm) U.S
40”(102 cm) CAN