Jotul F 100 USA Fan User Manual


 
5
Secure all connector joints with three sheet metal
screws. The connection to the stove flue collar takes
two sheetmetal screws.
For the best performance, the chimney connector
should be as short and direct as possible, including no
more than two 90° elbows.
The maximum vertical run of single wall stovepipe
should not exceed 10 ft. (305 cm).
The maximum horizontal run should not exceed 3 ft.
(92 cm) with a 1/4” rise per foot. Under no circumstance
should horizontal pipe be allowed to slant down toward
the chimney.
No part of the chimney connector may pass through
an attic or roof space, closet or other concealed space,
or through a floor or ceiling. All sections of the chimney
connectors must be accessible for cleaning. Where
passage through a wall or partition of combustible
construction is desired, the installation must conform
with NFPA 211 or CAN/CSA-B365, and is also addressed
in this manual.
Do not connect this stove to a chimney flue servicing
another appliance.
Install the Ashlip
Attach the ashlip to the front by engaging the center tab
with the slot located under the front door.
Assemble the Door Knob
Locate the white washer between the handle and the
knob.
Chimney Connector
Use 6” single wall or listed 6” double-wall stovepipe to
connect the stove to the chimney. Single wall stovepipe
must be black iron or stainless steel and have a minimum
thickness of 24 gauge. Do not use aluminum or galvanized
steel pipe for chimney connection - these materials are
not suitable for use with solid fuel.
Follow these guidelines regarding chimney connector
construction:
Do not use chimney connector as a chimney. It is
intended only for use as a connection device.
Each connector section must be oriented with the male
(crimped) end pointing toward the stove. See fig. 3.
Figure 1. Rear flue collar cut-out.
Cut at
these
points
Figure 2. Remove the Rear Flue Outlet Coverplate.
Figure 3. Chimney connector orientation.
Flue Gas
Direction
Toward
Stove
USA/Canada