Jotul F 100 USA Fan User Manual


 
10
Clearances to Walls and Ceilings
The clearances listed and diagramed in this manual have
been tested to UL and ULC standards and are the
minimum clearances to combustible materials
specifically established for the Jøtul F 100 USA.
A combustible surface is anything that can burn (i.e. sheet
rock, wall paper, wood, fabrics etc.). These surfaces are
not limited to those that are visible and also include
materials that are behind noncombustible materials.
If you are not sure of the combustible nature of a material,
consult your local fire officials.
Remember: “Fire Resistant” materials are considered
combustible; they are difficult to ignite, but will burn. Also
“Fire-rated” sheet rock is also considered combustible.
Contact your local building officials about restrictions
and installation requirements in your area.
See pages12-13 for complete clearance requirements and
diagrams.
Using Shields to Reduce Clearances
Chimney Connector Heat Shields:Chimney Connector Heat Shields:
Chimney Connector Heat Shields:Chimney Connector Heat Shields:
Chimney Connector Heat Shields: Use only connector
heat shielding listed for use with solid fuel heaters. The
connector heat shield must begin 1” above the lowest
exposed point of the connector pipe and extend vertically
a minimum of 25” (640 cm) above the top surface of the
stove.
Double Double
Double Double
Double
WW
WW
W
all Call C
all Call C
all C
onneconnec
onneconnec
onnec
tt
tt
t
oror
oror
or
::
::
: Listed double wall pipe is an
acceptable alternative to connector pipe heat shields.
When using double wWhen using double w
When using double wWhen using double w
When using double w
all call c
all call c
all c
onneconnec
onneconnec
onnec
tt
tt
t
oror
oror
or
,,
,,
,
Flue C Flue C
Flue C Flue C
Flue C
ollar Heaollar Hea
ollar Heaollar Hea
ollar Hea
tt
tt
t
Shield Kit 154997 must be installed on the stove.Shield Kit 154997 must be installed on the stove.
Shield Kit 154997 must be installed on the stove.Shield Kit 154997 must be installed on the stove.
Shield Kit 154997 must be installed on the stove.
WW
WW
W
all-Mounall-Moun
all-Mounall-Moun
all-Moun
ted Prted Pr
ted Prted Pr
ted Pr
otecotec
otecotec
otec
tion:tion:
tion:tion:
tion: When reducing clearances
through the use of wall mounted protection:
In In
In In
In
the Uthe U
the Uthe U
the U
.S.S
.S.S
.S
..
..
.
r r
r r
r
efef
efef
ef
er er
er er
er
tt
tt
t
o No N
o No N
o N
FPFP
FPFP
FP
A 211A 211
A 211A 211
A 211
,
Standard for Chimneys,
Fireplaces, Vents and Solid Fuel Burning Appliances
, for
acceptable materials, proper sizing and construction
guidelines.
In Canada,In Canada,
In Canada,In Canada,
In Canada,
refer to CAN/CSA-B365, refer to CAN/CSA-B365,
refer to CAN/CSA-B365, refer to CAN/CSA-B365,
refer to CAN/CSA-B365, Installation Code
for Solid-Fuel Burning Appliances and Equipment
, also
for acceptable materials, proper sizing and
construction guidelines.
USA/ CANADA
48”
122 cm
41”
104 cm
Figure 11. Alcove with Wall Protection.
Notice:
Many manufacturers have developed woodstove
accessories that permit clearance reduction. Use only
those accessories that have been tested by an
independent laboratory and carry the laboratory’s testing
mark. Be sure to follow all of the manufacturer’s
instructions.
Alcove Installation
The Jøtul F 100 USA can be installed in an Alcove as
diagrammed in figures 10 and 11.
1. The stove must be installed with listed double wall
pipe.
2. In a protected alcove installation both side walls and
rear wall must be protected per NFPA 211 or CAN/
CSA-B365. The wall protection must be elevated 1” (25
mm) from the floor and spaced at least 1” (25 mm) off
the combustible wall, using noncombustible spacers,
to allow for air circulation behind the shield.
3. The height of the wall protection including the bottom
air space must be 48” (121 cm).
4. Alcove floor protection must consist of a UL/ULC or
WHI listed hearth pad or a non combustible material
with a minimum R value of 2.0.
55”
140 cm
60”
153 cm
Figure 10. Alcove without Wall Protection.