Honeywell MS-9600LSE Smoke Alarm User Manual


 
70 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Programming Master Programming Level
If the selected address has been added to programming and a detector (such as a photoelectric
detector) with the selected address is physically installed on the SLC and is communicating with
the control panel, the following will be displayed:
To change the programming for the displayed detector, press the keyboard ‘down’ arrow key to
view the Edit Detector screens.
In the preceding example:
Normal - indicates that the detector with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device
ZNNN - represents the first of five possible software zones that the detector is assigned to
(NNN = the three digit zone number from 000 - 099)
V or * - indicates whether or not alarm verification is enabled (V = alarm verification
enabled and * = alarm verification disabled)
1D017 - represents the Loop, Device type and Device address (1 = SLC Loop 1, D=Detector
and 017 = Detector Address 017)
NORMAL SMOKE (PHOTO)
*********************
ZNNN
V 1D017
Edit Detector Screen #1