MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 163
Read Status Operating Instructions
Pressing the down arrow key, while viewing the screen shown on the previous page, will allow the
operator to view additional programming information about the selected device, such as:
Enable/Disable Status
Device Type
Alarm Verification On/Off
Walktest Yes/No
PAS (Positive Alarm Sequence) Yes/No
Pre-Signal Yes/No
Zone Assignments (five maximum)
Chamber Reading
Adjective/Noun descriptor
Silenceable Yes/No (for control modules)
4.22.2 Zones
Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:
From the preceding screens, the control panel operator can view:
Zones Installed - all software zones programmed into the system (99 maximum)
Zones Enabled - all software zones that are enabled
Zones Disabled - all software zones that have been disabled
Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98
reserved for Pre-signal and 99 reserved for future use
Zone Type - the Type assigned to each installed zone (default is Alarm)
Zone Message - the message assigned to each installed zone
READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER
Read Status Screen #1
ZONES
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zones Screen #1
ZONES
1=SPECIAL PURPOSE
2=ZONE TYPE
3=ZONE MESSAGE
Zones Screen #2