SDC / DHC Operation
EN2H-0221GE51 R0808 97
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
11 Constant tem-
perature setpoint
(only if output was
set to constant
regulator)
10 ... 95°C
20
12 Minimum
temperature limit
10°C to setting value of
parameter 13
20
13 Maximum
temperature limit
Setting value of parameter 12 to
Setting value of parameter 30 in
"Heat generator" menu (OEM
maximum limit)
75
14 Temperature
increase of heating
circuit
–5 ... 20 K Mixed
heating
circuit = 4
15 Follow-up time of
pump
0 ... 60 min 5
OFF OFF
1 Functional heating
16 Screed function
2 Screed-drying heating
17 Return maximum
temperature limit
10 ... 90 °C
90
18* P part X
P
1 ... 50 %/K 2
19* Sampling time T
s
1 ... 600 s 20
20* I part T
n
1 ... 600 s 270
21* Actuator runtime 10 ... 600 s 120
1 Continuous control
signal in end position
1 22* Actuator end
position function
2 Control signal
suppressed at end
position (actuator de-
energised)
23 Room control C-
factor (SDW 30
only)
1 ... 100 8