Honeywell EN2H-0221GE51 R0808 Heating System User Manual


 
Hydraulic Components SDC / DHC
194 EN2H-0221GE51 R0808
Tank parallel operation (combined operation: hot-water
loading/heating)
WEZ1 WEZ2
WEZ3 WEZ4 WEZ5
10s 10s 1min 1min
2min 2min 2min 2min
Connection up to the stage of parameter 09 with minimum
delay for hot-water loading
In case of further need via heating, further connection with
configured delay of parameter 02
Reversion with configured delay parameter 03
7.3.5.2 Circulation pump (CIR.)
This function is only available, if a variable output is assigned to a
circulation pump
The output controls a hot-water circulation pump.
The use of the economy interval minimises the usual circulation
losses owing to adjustable switch-on intervals during operation
and determines the standstill time of the hot-water circulation
pump within an adjustable period (economy interval).
This parameter determines the length of the period and hence the
duration of the pause in a circulation pump pulse operating mode.
Economy interval
Pause
= Economy interval
Period duration
- Economy
interval
Pulse
The switching-on degree is calculated from the ratio:
n = Pulse time/Period duration x 100 (%)
Example:
With an standstill time of 15 min. and a period of 20 min., the
circulation pump will run for 5 min. before the subsequent pause
of 15 min.
The following is used to calculate the switching-on degree:
n = 5/20 = 25%
In this function a hot-water circulation pump can be coupled to an
existing automatic program of a control circuit with regard to the
NOTE
Function
Economy interval
(pulse)
Economy interval
(period duration)
Switching times