Honeywell EN2H-0221GE51 R0808 Heating System User Manual


 
Operation SDC / DHC
94 EN2H-0221GE51 R0808
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
12 Minimum
temperature limit
10°C to setting value of
parameter 13
20
13 Maximum
temperature limit
Setting value of parameter 12 to
Setting value of parameter 30 in
"Heat generator" menu (OEM
maximum limit)
75
14 Temperature
increase of heating
circuit
–5 ... 20 K Direct
heating
circuit = 0
15 Extended pump
over-run
0 ... 60 min 5
OFF OFF
1 Functional heating
16 Screed function
2 Screed-drying heating
23 Room control
C-factor (SDW 30
only)
1 ... 100 8
24 Room control T
n
(SDW 30 only)
5 ... 240 min 35
STBY Standby STBY 25 Holiday operating
mode
RED Lowering operation
26 Room setpoint
ramp
OFF, 0.5 to 60 K/h OFF
OFF OFF
1 Adaption off
2 Adaption on
41 Switch-on
optimisation
3 Adaption restart
42 Min. pre-heat time 0 ... setting value of parameter 43 0,5
43 Max. pre-heat time Setting value of parameter 42 to
30 h
5
44 Min. jump back
temperature
0 ... 30°C 5
45 Without room
sensor
0 ... 10°C 1