Honeywell 800-04433V1 Smoke Alarm User Manual


 
iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide
7
STEP 6 – Configure the Fire Panel
1. Ensure the Telco Fault on the panel is enabled. Then choose a setting that is no higher than 90
seconds (or as close to that) as the panel allows.
2. Ensure no more than 1 pause character (usually a comma) is programmed into the dialing string
(usually 2 seconds). Note, this is necessary since the Dialer Capture Module waits only 3 seconds
after the phone number is dialed. Having more than 3 seconds of pause time will cause it to think
the phone number is complete and cause it to generate the high-low tones at an incorrect moment.
STEP 7 – Test the System
1. Close the Wall Outlet Box, then close and lock the cabinet cover.
2. Refer to the fire panel's installation/operation guide the testing procedure.
3. (Notify the monitoring station that a test will be conducted.) Test the system to ensure it is
operating.
iPGSM-COM Trouble Detection Information
Telco 1 is used for the Fire Panel to output contact ID messages to the iPGSM-COM, and Telco 2 is used by
the iPGSM-COM to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use
Telco 2 to report events if there are no faults in the iGSM Communications module.
Fault Condition Indication to Fire Panel
PowerBoost1 fault Telco 2 is cut.
iGSM Communications Module fault
Failure of one of the two
communications paths.
Telco 2 is cut.
Failure of both communications
paths.
Telco 1 and 2 are cut.
Dialer Capture Module buffer is full. Hang up. (Panel will retry, giving the buffer a chance to empty.)