iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide
10
iGSM Communications Module Information
TB 1
6
7
8
5
10
11
9
2
3
4
1
PRIMARY POWER: 9 - 16.5 VAC
CURRENT: 900mA PEAK, 70mA STANDBY
BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP
FCC:XXXXXXXXXX IC: YYYYYYYYYY
RSSI
M0
M1
GPRS
IBS
iPGSM-COM-002-V0
RSSI / Mode
and
status LEDs
ON – Message transmission pending.
QUICK PERIODIC BLINK – Normal.
FAST BLINK – Message waiting for network ACK.
SLOW BLINK – Idle power abnormal.
SLOW BLINK – In unison with green LED,
registratration in progress.
Ethernet Link/Activity
GREEN
ON – Ethernet Link detected.
OFF – No link detected.
FAST BLINK – Transmitting/Receiving Data.
Link Speed
GREEN
Network Collision
YELLOW
Note: If all LEDs FAST BLINK in unison with
the RSSI LEDs this indicates a Hardware Error.
ON – No contact with network.
OFF – Normal.
SLOW BLINK – Loss of communication with the
Dialer Capture Module
(ECP fault).
ON – NOT registered with AlarmNet.
OFF – Registered with AlarmNet.
FAST BLINK – Download session with Compass
in progress.
SLOW BLINK – In unison with yellow LED,
registration in progress.
Mode
Switch
Tamper
Switch
GRN
YEL
RED
ECP OFF OFF
Zone (NOT USED) ON OFF
4204 (NOT USED) OFF ON
2 - 4204 (NOT USED) ON ON
MODULE'S RECEIVED SIGNAL STRENGTH (RSSI)
When the Mode Switch is NOT depressed, LED 1 will illuminate red.
The remaining LEDs indicate RSSI (Received Signal Strength).
MODULE'S OPERATION MODE
When the Mode Switch IS depressed, LED 1 will be OFF.
LEDs 2 and 3 indicate the module's communication mode with the Dialer Capture Module.
Mode LED 2 (yellow) LED 3 (yellow)
MODULE'S STATUS
When the Mode Switch IS depressed, LED 1 will be OFF.
LEDs 4, 5, and 6 indicate the module's Status.
FAST BLINK - Module registered, second
site available, excellent signal strength.
LED 4 (green) LED 5 (green) LED 6 (green)
ON - Connected to
Internet.
ON - Module registered, no second
site available.
ON - GPRS service
available.
OFF - No GPRS service
available
OFF - Module not registered with
network carrier.
FAST BLINK - GPRS in
use.
SLOW BLINK - Module registered, second
site available, and low signal strength.
NORMAL BLINK - Module registered, second
site available, acceptable signal strength.
OFF - Not connected
to Internet.
7720P
Programmer
Port
BLINKING – Network collision detected.
OFF – Normal.
ON – 100 MB/S link to Internet.
OFF – 10 MB/S link to Internet.
FAST BLINK – No network contact AND loss of communi-
cation with the