Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 105
Appendix D: Programmed Activation by FACP
The Audio Command Center Zone Split system (ACC-25/50ZS/T) can be automatically controlled
by any FACP. The following table lists the available audio features and the control signals that are
required from the FACP.
Column Descriptions for Table D.1
• FA C P - the Fire Alarm Control Panel being used
• ACC-ZPMK S1 DIP switch Setting - the DIP switch setting on the ACC-ZPMK in accordance
with the FACP installed
• Individual Audio Zone Control via ACS/ANN-BUS Link - ACS or ANN-BUS compatible
FACPs can control each audio zone on the ACC-25/50ZS or ACC-25/50ZST (refer to the
FACP specific programming sections in this Appendix)
• Individual Control of All Messages - control of all voice messages in the ACC-25/50ZS or
ACC-25/50ZST can be accomplished through the ACS/ANN-BUS link or by triggering the
CMD inputs (refer to the FACP specific programming sections in this Appendix.)
FACP
ACC-
ZPMK
S1 DIP
Switch
Settings
1 2 3
Individual
Audio
Zone Control
via
Serial Link
Individual Control of
All Messages
Simultaneous
Activation of All
Audio Zones
1
Fire Fighter
Telephone
Remote
Annunciation
via
Serial Link
ACS ANN ACS ANN CMD ACS ANN
Non-ACS/ANN-BUS FACP or
MS-9200UD version 1
2
0 0 0 No No No No Yes Yes No No
MS-5210UD 0 0 1 Yes No No
3,4
No Yes
3
No No No
MS-9200 0 1 0 Yes No No
3
No Yes
5
Yes Yes No
MS-9600 version 1 0 1 1 Yes No No
4
No Yes
5
Yes Yes No
MS-9600 version 2 or 3 1 0 0 Yes No No No Yes
6
Yes Yes
7
No
MS-9200UDLS or
MS-9200UD version 2 or 3
1 0 1 Yes No Yes No Yes
7
Yes Yes
7
No
MS-9200UDLS version 4 or higher 1 1 0 Yes Yes Yes Yes Yes Yes Yes
8
Yes
MS-9600LS version 4 or higher 1 1 0 Yes Yes Yes Yes Yes Yes Yes
7
Yes
MS-5UD-3/7 or MS-10UD-3/7
version 2 or higher
1 1 0 No Yes No Yes Yes
9
Yes No No
future 1 1 1
Table D.1 FACP Message/Zone Control of the ACC-25/50ZS/T
1 There may be up to an 8 second delay between alarm indication on the FACP and activation of the message and
speaker zones on the ACC-25/50ZS/T.
2 ACS link control utilizing the MS-9200UD version 1 is not available.
3 The MS-5210UD can control up to 5 messages via the ACS link using the ACM-8RF Relay Module.
4 Only Message #1 can be automatically activated by the FACP via ACS control.
5 Program Software Zone 32 in the FACP to activate all the Audio Zones on the ACC-25/50ZS/T.
6 For CMD Input Control using version 2 or higher, set the ACC-ZPMK DIP switch for MS-9600 version 1.
7 Enable ACS address 07 to annunciate remote FFT locations.
8 Enable ACS address 05 to annunciate remote FFT locations.
9 For CMD Input Control using the MS-5UD-3/7 or MS-10UD-3/7, set the ACC-ZPMK DIP switch for
Non-ACS/ANN-BUS FACP.