E. Combustible Mantel
Refer to the shaded areas of Figure 11.4 for locations and dimensions of a combustible mantel.
A combustible mantel may be positioned no lower than 12 5/8 in. (321 mm) above the top of the replace opening.
A combustible mantel may have a maximum depth of 10 in. (254 mm).
Combustible trim and materials cannot be placed within 6 in. (152 mm) of the replace opening (top or sides).
Combustible materials projecting more than 1 1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) above the top
of the replace opening.
Combustible trim must not cover the metal surfaces of the replace.
Mantel clearance is in accordance with Section 7-3.3.3 of ANSI/NFPA211.
Mantel
7 ft (2134 mm)
minimum
base of fireplace
to ceiling
Combustible wall
2 x 4 stud wall
Standoffs
Measured from top of fireplace opening
10 in./254 mm
1 1/2 in./38 mm
maximum
12 5/8 in./321 mm
minimum
12 in./305 mm
minimum
6 in./152 mm
minimum
Combustible
decorative facing
Non-combustible
decorative facing
such as steel, iron,
brick, tile, concrete,
slate, glass, plasters
Seal joint with
non-combustible
sealant
Grid represents
1 in. squares.
Figure 11.4 Clearances to Mantels or other Combustibles above Fireplace
Heatilator • CL36D, CR36D • 12538 • Rev V • 05/09