Heat & Glo • 6000GLX-IPI-S/-R, 6000GLX-IPILP-S/-R • 2101-900 Rev. Q • 11/0824
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
H
1
V
1
Figure 7.3
Figure 7.4
Top Vent - Horizontal Termination
Top Vent - Horizontal Termination
One Elbow
Two Elbows
Note: For corner installations: A 6 inch (152
mm) section of straight pipe may need to
be attached to the appliance before a 90º
elbow, to allow the vent pipe to clear the top
standoffs.
Note: For corner installations: A 6 inch
(152 mm) section of straight pipe may
need to be attached to the appliance
before a 90º
elbow, to allow the vent
pipe to clear the top standoffs.
V
1
Minimum H
1
Maximum
Elbow only 2 ft 610 mm
1 ft. 305 mm 3 ft. 914 mm
2 ft. 610 mm 6 ft. 1.8 m
3 ft. 914 mm 11 ft. 3.4 m
4 ft. 1.2 m 20 ft. 6.1 m
V
1
+ H
1
= 40 ft. (12.2 m) Maximum
H
1
= 20 ft. (6.1 m) Maximum
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles
between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around
venting and fi restop systems.
• Install wall shield and ceiling fi restops as speci-
fi ed.
Failure to keep insulation or other material away
from vent pipe may cause fi re.
Note: The 6000 series fi replaces can adapt to
SLP series vent pipe, if desired.
When venting off the top of the unit, use a DVP-2SL adapter and
a minimum 48 inch vertical section of SLP series vent pipe.
After the 48 inch vertical section, the venting table rules
must be followed. The fi rst 48 inch vertical section is NOT
counted as part of the vertical components in the table. It is
still counted as part of the overall maximum run. All venting
table rules for the vent run must still be followed.
Example: DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal
SLP pipe 7 ft. min. vertical = 11 ft. max. horizontal
V
1
Minimum H
1
+ H
2
Maximum
Elbow only 1 ft. 305 mm
6 in. 152 mm 2 ft. 610 mm
1 ft. 305 mm 2 ft. 610 mm
2 ft. 610 mm 4 ft. 1.2 m
3 ft. 914 mm 9 ft. 2.7 m
4 ft. 1.2 m 18 ft. 5.5 m
5 ft. 1.5 m 20 ft. 6.1 m
V
1
+ H
1
+ H
2
= 40 ft. (12.2 m) Maximum
H
1
+ H
2
= 20 ft. (6.1 m) Maximum
Fire Risk.
• When using DVP-HRC-SS and DVP-HRC-ZC-
SS termination caps on top vented fi replaces, a
6 inch minimum vertical vent section is required
before installing fi rst elbow.
WARNING
WARNING
E. Vent Diagrams