Heat & Glo LifeStyle 6000CMOD-IPI Indoor Fireplace User Manual


 
47
Heat & Glo • 6000CMOD-IPI, 8000CMOD-IPI • 2241-900 Rev. H • 5/12
13
13
Finishing
A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as speci ed. Framing closer than the minimums list-
ed must be constructed entirely of noncombustible materials
(i.e., steel studs, concrete board, etc.)
Figure 13.2 Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
Figure 13.1 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
Combustible Mantels
Combustible Mantel Legs or Wall Projections
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
5
10
11
12
2-1/2
13
14
15
16
17
18
19
32
TO CEILING
9
10
11
12
8
7
6
5
4
3
25
18
A
B
INTERIOR WALL
TOP VIEW
MANTEL LEG OR WALL PROJECTIONS
FIREPLACE OPENING
Note: All
measurements
in inches.
If A minimum is ____, then B maximum is_____.
A
Inches
2-7/16 3-7/16 4-7/16 5-7/16 6-7/16 7-7/16
Millimeters
62 87 113 138 164 189
B
Inches
12345
Millimeters
25 51 76 102 127
Note: Measurement is taken from top of the opening,
NOT the top of the replace.
3/8 IN.
1-3/4 IN.
3/8 IN.
The CMOD door will overlap the appliance. See Figure
13.3 and 13.4.
Figure 13.3 Appliance Surround
Figure 13.4 Door Overlaps Surround