Heat & Glo LifeStyle 6000CMOD-IPI Indoor Fireplace User Manual


 
27
Heat & Glo • 6000CMOD-IPI, 8000CMOD-IPI • 2241-900 Rev. H • 5/12
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
Figure 7.4
Two Elbows
Note: For corner installations: A 6 inch
(152 mm) section of straight pipe may
need to be attached to the appliance
before a 90º
elbow, to allow the vent
pipe to clear the top standoffs.
6000CMOD-IPI
V
1
Minimum H
1
+ H
2
Maximum
Elbow only Not allowed
6 in. 152 mm 2 ft. 610 mm
1 ft. 305 mm 4 ft. 1.2 m
1-1/2 ft. 457 mm 11 ft. 3.4 m
2 ft. 610 mm 17 ft. 5.2 m
2-1/2 ft. 762 mm 20 ft. 6.1 m
V
1
+ H
1
+ H
2
= 40 ft. (12.2 m) Maximum
H
1
+ H
2
= 20 ft. (6.1 m) Maximum
V
1
= 1 ft. (305 mm) Minimum
8000CMOD-IPI
V
1
Minimum H
1
+ H
2
Maximum
Elbow only Not allowed
6 in. 152 mm Not allowed
1 ft. 305 mm 2 ft. 610 mm
2 ft. 610 mm 4 ft. 1.2 m
3 ft. 914 mm 6 ft. 1.8 m
4 ft. 1.2 m 8 ft. 2.4 m
6 ft. 1.8 m 12 ft. 3.6 m
10 ft. 3.0 20 ft. 6.1 m
V
1
+ H
1
+ H
2
= 40 ft. (12.2 m) Maximum
H
1
+ H
2
= 20 ft. (6.0 m) Maximum
V
1
= 1 ft. (305 mm) Minimum