Heat & Glo LifeStyle 6000 XLT Indoor Fireplace User Manual


 
1
Approval Listings
and Codes
Appliance Certification
The Heat-N-Glo fireplace models discussed in this
Installers Guide
have been tested to certification
standards and listed by the applicable laboratories.
CERTIFICATION
MODEL LABORATORY TYPE STANDARD
8000DVTFL Underwriters Direct Vent ANSI Z21.50•CGA2.22
Laboratories Decorative
6000DVTFL Underwriters Direct Vent ANSI Z21.50•CGA2.22
Laboratories Decorative
6000ARCH Underwriters Direct Vent ANSI Z21.50•CGA2.22
Laboratories Decorative
6000XLT Underwriters Direct Vent
Laboratories Decorative ANSI
Z21.50•CGA2.22
Wall Furnace Z21.44/IR#41/CANI-2.19
SL-42DVT Underwriters Direct Vent ANSI Z21.50•CGA2.22
Laboratories Decorative
Installation Codes
The fireplace installation must conform to local codes. Before installing the
fireplace, consult the local building code agency to ensure that you are in
compliance with all applicable codes, including permits and inspections.
In the absence of local codes, the fireplace installation must conform to the
National Fuel Gas Code ANSI Z223.1 (in the United States) or the CAN/CGA-
B149 Installation Codes (in Canada). The appliance must be electrically
grounded in accordance with local codes or, in the absence of local codes with
the National Electric Code ANSI/NFPA No. 70 (in the United States), or to the
CSA C22.1Canadian Electric Code (in Canada).
These models may be installed in a bedroom or bed-sitting room in the U.S.A.
and Canada.
High Altitude Installations
U.L. Listed gas fireplaces are tested and approved for elevations from 0 to 2,000
feet in the U. S. A. and from 0 to 4,500 feet in Canada.
When installing this fireplace at an elevation above 2,000 feet (in the United
States), it may be necessary to decrease the input rating by changing the
existing burner orifice to a smaller size. Input should be reduced four percent
(4%) for each 1,000 feet above sea level, unless the heating value of the gas has
been reduced, in which case this general rule will not apply. To identify the proper
orifice size, check with the local gas utility.
When installing this fireplace at an elevation between 2,000 and 4,500 feet (in
Canada), the input rating must be reduced by ten percent (10%).
When installing this fireplace at an elevation above 4,500 feet (in Canada), check
with local authorities.
Consult your local gas utility for assistance in determining the proper orifice for
your location.
1
Approvals
and Codes