Heat & Glo LifeStyle 6000 GDVFL Indoor Fireplace User Manual


 
18
For round cap
termination:
1. Secure the 8-5/8 inch
(219 mm) pipe, using
the exterior pipelock
hole on the round
flange of the wall
firestop.
For trapezoidal
termination:
1. Screw the cap to the
exterior wall through
the flanges in the cap.
2. Seal the joint between
the pipe and the
exterior firestop.
Figure 18. Round and Trapezoid Termination
Caps
WARNING
THE BOTTOM OF THE VENT
TERMINATION CAP MUST BE A
MINIMUM OF 12 INCHES (305 MM)
ABOVE GROUND LEVEL (GRADE). THE
TOP OF THE CAP MUST BE A MINIMUM
OF 18 INCHES (457 MM) BELOW
COMBUSTIBLE MATERIAL, SUCH AS A
DECK, AND THE SIDE OF THE CAP
MUST BE A MINIMUM OF 6 INCHES (152
MM) AWAY FROM A PARALLEL OUTSIDE
WALL. VENTING TERMINALS SHALL
NOT BE RECESSED INTO A WALL OR
SIDING. SEE THE FOLLOWING
DIAGRAM FOR VENT TERMINATION
CLEARANCES.