Heat Controller HBH/V Heat Pump User Manual


 
20 7.0 4.5 10.3 0 0 0 0 0 0 0 710 11.6 1.05 8.2 85.1 3.25
20 7.0 4.5 10.3 0 0 0 0 0 0 0 825 11.7 1.02 8.4 83.2 3.38
30 3.5 1.2 2.8 620 22.2 14.0 0.63 0.58 24.1 38.3 710 13.6 1.09 10.1 87.8 3.66
30 3.5 1.2 2.8 725 22.5 14.7 0.65 0.59 24.4 38.3 825 13.8 1.06 10.3 85.5 3.81
30 5.8 2.9 6.6 620 22.4 14.0 0.63 0.57 24.3 39.2 710 14.2 1.09 10.7 88.5 3.81
30 5.8 2.9 6.6 725 22.7 14.7 0.65 0.58 24.7 39.2 825 14.4 1.06 10.9 86.1 3.97
30 7.0 4.1 9.4 620 22.5 14.0 0.62 0.56 24.4 39.8 710 14.4 1.09 10.9 88.8 3.86
30 7.0 4.1 9.4 725 22.8 14.7 0.65 0.57 24.7 39.8 825 14.6 1.06 11.1 86.3 4.02
40 3.5 1.1 2.5 620 22.9 15.1 0.66 0.65 25.1 35.3 710 16.1 1.15 12.3 90.9 4.08
40 3.5 1.1 2.5 725 23.3 15.8 0.68 0.66 25.5 35.3 825 16.2 1.12 12.6 88.2 4.25
40 5.8 2.6 5.9 620 23.1 15.1 0.65 0.61 25.2 37.9 710 16.7 1.15 13.0 91.8 4.25
40 5.8 2.6 5.9 725 23.4 15.9 0.68 0.62 25.5 37.9 825 16.9 1.12 13.3 89.0 4.42
40 7.0 3.6 8.4 620 23.2 15.1 0.65 0.6 25.2 38.3 710 16.9 1.16 13.2 92.1 4.30
40 7.0 3.6 8.4 725 23.5 15.9 0.68 0.61 25.6 38.3 825 17.1 1.12 13.5 89.2 4.47
50 3.5 1.0 2.3 620 22.7 15.4 0.68 0.74 25.2 30.7 710 18.3 1.18 14.5 93.9 4.56
50 3.5 1.0 2.3 725 23.0 16.2 0.70 0.75 25.6 30.7 825 18.5 1.14 14.8 90.8 4.75
50 5.8 2.4 5.6 620 22.9 15.5 0.67 0.69 25.3 33.4 710 19.1 1.18 15.2 94.8 4.73
50 5.8 2.4 5.6 725 23.3 16.3 0.70 0.70 25.6 33.4 825 19.3 1.15 15.5 91.6 4.93
50 7.0 3.4 7.9 620 23.0 15.5 0.67 0.67 25.3 34.1 710 19.3 1.18 15.4 95.1 4.78
50 7.0 3.4 7.9 725 23.3 16.3 0.70 0.68 25.6 34.1 825 19.5 1.15 15.7 91.9 4.98
60 3.5 1.0 2.2 620 21.9 15.3 0.70 0.85 24.8 25.9 710 20.4 1.21 16.5 96.6 4.93
60 3.5 1.0 2.2 725 22.2 16.1 0.73 0.86 25.1 25.9 825 20.6 1.18 16.8 93.2 5.13
60 5.8 2.3 5.2 620 22.4 15.5 0.69 0.78 25.1 28.6 710 21.2 1.22 17.3 97.7 5.10
60 5.8 2.3 5.2 725 22.7 16.3 0.72 0.80 25.4 28.6 825 21.5 1.18 17.6 94.1 5.31
60 7.0 3.2 7.4 620 22.5 15.5 0.69 0.77 25.1 29.4 710 21.5 1.22 17.5 98.0 5.15
60 7.0 3.2 7.4 725 22.9 16.3 0.71 0.78 25.5 29.4 825 21.7 1.19 17.8 94.3 5.36
70 3.5 0.9 2.1 620 20.7 14.8 0.72 0.97 24.0 21.4 710 22.4 1.23 18.4 99.2 5.35
70 3.5 0.9 2.1 725 21.0 15.6 0.74 0.98 24.3 21.4 825 22.7 1.19 18.8 95.4 5.57
70 5.8 2.1 4.9 620 21.4 15.1 0.71 0.90 24.4 23.8 710 23.3 1.24 19.3 100.4 5.52
70 5.8 2.1 4.9 725 21.7 15.9 0.73 0.91 24.8 23.8 825 23.5 1.20 19.6 96.4 5.75
70 7.0 3.0 7.0 620 21.6 15.2 0.71 0.88 24.6 24.5 710 23.5 1.24 19.5 100.7 5.57
70 7.0 3.0 7.0 725 21.9 16.0 0.73 0.89 24.9 24.5 825 23.8 1.20 19.9 96.7 5.80
80 3.5 0.8 1.9 620 19.3 14.2 0.73 1.10 23.1 17.5 710 24.4 1.25 20.3 101.8 5.73
80 3.5 0.8 1.9 725 19.6 14.9 0.76 1.12 23.4 17.5 825 24.6 1.21 20.7 97.7 5.97
80 5.8 2.0 4.6 620 20.1 14.5 0.72 1.03 23.6 19.5 710 25.3 1.26 21.2 103.0 5.90
80 5.8 2.0 4.6 725 20.4 15.3 0.75 1.04 23.9 19.5 825 25.6 1.22 21.6 98.7 6.15
80 7.0 2.8 6.5 620 20.3 14.6 0.72 1.01 23.7 20.1 710 25.6 1.26 21.5 103.4 5.95
80 7.0 2.8 6.5 725 20.6 15.4 0.75 1.02 24.0 20.1 825 25.9 1.22 21.9 99.0 6.20
85 3.5 0.8 1.9 620 18.7 13.9 0.75 1.18 22.7 15.9 710 25.3 1.26 21.2 103.0 5.91
85 3.5 0.8 1.9 725 18.9 14.6 0.77 1.19 23.0 15.9 825 25.6 1.22 21.7 98.7 6.15
85 5.8 1.9 4.5 620 19.3 14.2 0.73 1.10 23.1 17.5 710 26.3 1.27 22.2 104.3 6.08
85 5.8 1.9 4.5 725 19.6 14.9 0.76 1.12 23.4 17.5 825 26.6 1.23 22.6 99.9 6.33
85 7.0 2.7 6.3 620 19.5 14.3 0.73 1.08 23.2 18.0 710 26.6 1.27 22.5 104.7 6.13
85 7.0 2.7 6.3 725 19.8 15.0 0.76 1.10 23.6 18.0 825 26.9 1.24 22.9 100.2 6.38
90 3.5 0.8 1.8 620 18.0 13.7 0.76 1.25 22.3 14.4 710 26.3 1.27 22.2 104.3 6.08
90 3.5 0.8 1.8 725 18.3 14.4 0.78 1.27 22.6 14.4 825 26.6 1.23 22.6 99.8 6.33
90 5.8 1.9 4.4 620 18.6 13.8 0.74 1.18 22.6 15.8 710 27.3 1.28 23.1 105.6 6.25
90 5.8 1.9 4.4 725 18.9 14.6 0.77 1.20 22.9 15.8 825 27.6 1.24 23.6 101.0 6.51
90 7.0 2.7 6.2 620 18.8 13.9 0.74 1.16 22.7 16.3 710 27.6 1.28 23.4 106.0 6.30
90 7.0 2.7 6.2 725 19.1 14.7 0.77 1.17 23.1 16.3 825 27.9 1.25 23.9 101.3 6.56
100 3.5 0.8 1.8 620 16.6 13.0 0.78 1.41 21.4 11.7 0 0 0 0 0 0
100 3.5 0.8 1.8 725 16.8 13.7 0.81 1.43 21.7 11.7 0 0 0 0 0 0
100 5.8 1.8 4.2 620 17.1 13.2 0.77 1.34 21.7 12.7 0 0 0 0 0 0
100 5.8 1.8 4.2 725 17.4 13.8 0.80 1.36 22.0 12.7 0 0 0 0 0 0
100 7.0 2.6 6.0 620 17.3 13.3 0.77 1.32 21.8 13.1 0 0 0 0 0 0
100 7.0 2.6 6.0 725 17.5 13.9 0.79 1.34 22.1 13.1 0 0 0 0 0 0
110 3.5 0.7 1.7 620 15.5 12.7 0.82 1.59 20.9 9.7 0 0 0 0 0 0
110 3.5 0.7 1.7 725 15.7 13.4 0.85 1.61 21.2 9.7 0 0 0 0 0 0
110 5.8 1.7 4.0 620 15.8 12.7 0.80 1.53 21.0 10.3 0 0 0 0 0 0
110 5.8 1.7 4.0 725 16.0 13.3 0.83 1.55 21.3 10.3 0 0 0 0 0 0
110 7.0 2.5 5.7 620 16.0 12.7 0.80 1.50 21.1 10.6 0 0 0 0 0 0
110 7.0 2.5 5.7 725 16.2 13.4 0.83 1.52 21.4 10.6 0 0 0 0 0 0
120 3.5 0.7 1.6 620 14.5 12.6 0.87 1.84 20.8 7.9 0 0 0 0 0 0
120 3.5 0.7 1.6 725 14.7 13.3 0.90 1.86 21.1 7.9 0 0 0 0 0 0
120 5.8 1.7 3.9 620 14.8 12.5 0.85 1.73 20.7 8.6 0 0 0 0 0 0
120 5.8 1.7 3.9 725 15.0 13.2 0.88 1.76 21.0 8.6 0 0 0 0 0 0
120 7.0 2.4 5.5 620 14.9 12.5 0.84 1.71 20.7 8.7 0 0 0 0 0 0
120 7.0 2.4 5.5 725 15.1 13.2 0.87 1.73 21.0 8.7 0 0 0 0 0 0
EWT
°F
GPM
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT
Airow
CFM
TC SC
Sens/Tot
Ratio
kW HR EER
Airow
CFM
HC kW HE LAT COP
20 Operation not recommended
30
40
50
60
70
80
85
90
100
Operation not recommended
110
120
Engineering Design Guide HBH/V SERIES Heat Controller, Inc.
Performance Data
Selection Notes
For operation in the shaded area when water is used
in lieu of an anti-freeze solution, the LWT (Leaving
Water Temperature) must be calculated. Flow must be
maintained to a level such that the LWT is maintained
above 40°F [4.4*C] when the JW3 jumper is not clipped
(see example below). This is due to the potential of the
refrigerant temperature being as low as 32°F [0°C] with
40°F [4.4°C] LWT, which may lead to a nuisance cutout
due to the activation of the Low Temperature Protection.
JW3 should never be clipped for standard range
equipment or systems without antifreeze.
Example:
At 50°F EWT (Entering Water Temperature) and 2.25
gpm/ton, a 3 ton unit has a HE of 27,300 Btuh. To
calculate LWT, rearrange the formula for HE as follows:
HE = TD x GPM x 500, where HE = Heat of Extraction
(Btuh); TD = temperature difference (EWT - LWT) and
GPM = U.S. Gallons per Minute.
TD = HE / (GPM x 500)
TD = 27,300 / (6.75 x 500)
TD = 8°F
LWT = EWT - TD
LWT = 50 - 8 = 42°F
In this example, as long as the EWT does not fall below 50°F, the system will operate as designed. For EWTs below
50°F, higher ow rates will be required (open loop systems, for example, require at least 2 gpm/ton when EWT is
below 50°F).
7