Heat Controller HBH/V Heat Pump User Manual


 
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide
Model
Fan
Speed
Rated
Airow
Min
CFM
Airow (cfm) at External Static Pressure (in. wg)
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
HBH/V 015
HS HI
525 375
774 764 755 745 735 715 696 676 637 519
HS MED 735 725 706 696 686 676 657 657 647 637 617 588 480
HS LOW 657 647 627 617 608 598 588 578 568 568 559 519
HBH/V 018
HS HI
600 450
0 0 0 774 764 755 745 735 715 696 676 637 519
HS MED 735 725 706 696 686 676 657 657 647 637 617 588 480
HS LOW 657 647 627 617 608 598 588 578 568 568 559 519
HBH/V 024
HS HI
800 600
979 903 798 665
HS MED 988 960 922 846 713 589
HS LOW 979 960 931 912 884 855 827 751 675
HBH/V 030
HS HI
1000 750
1102 988 874 760 713
HS MED 1074 1026 979 884 779 713
HS LOW 998 988 979 960 941 931 912 893 865 836 798 713
HBH/V 036
HS HI
1200 900
1484 1455 1426 1358 1251 1135 931
HS MED 1319 1310 1300 1290 1280 1271 1261 1242 1222 1213 1193 1116 1038 883
HS LOW 999 989 980 980 970 970 960 951 931 922 902
HBH/V 042
HS HI
1350 1050
1473 1463 1444 1425 1397 1387 1378 1311 1178 1026
HS MED 1321 1311 1302 1292 1283 1273 1254 1245 1235 1216 1188 1121 1026
HS LOW
HBH/V 048
HS HI
1600 1200
1957 1938 1910 1862 1786 1701 1577 1435
HS MED 1948 1948 1938 1919 1891 1872 1843 1824 1796 1767 1739 1691 1625 1539 1416 1254
HS LOW 1758 1758 1748 1739 1720 1710 1691 1672 1644 1615 1587 1520 1435 1311 1159 0
HBH/V 060
HS HI
2000 1500
2352 2352 2342 2332 2323 2313 2293 2274 2254 2225 2195 2156 2087 2019 1940 1852
HS MED 2117 2117 2107 2107 2097 2068 2038 2019 1999 1989 1980 1940 1891 1842 1460 1715
HS LOW 1891 1891 1882 1882 1872 1862 1852 1852 1842 1833 1813 1793 1764 1715 1666 1588
Black areas denote ESP where operation is not recommended.
Units factory shipped on medium speed. Other speeds require eld selection.
All airow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
Only two speed fan (H & M) available on 575V units.
Performance stated is at the rated power supply, performance may vary as the power supply varies from the rated.
Blower Performance Data
High Static