Heat Controller HBH/V Heat Pump User Manual


 
Engineering Design Guide HBH/V SERIES Heat Controller, Inc.
Electrical Data -
Standard Unit
HB
Model
Voltage
Code
Rated
Voltage
Voltage
Min/
Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY RLA LRA
006 1
208-230/60/1 197/254 1 3.3 17.7 0.40 3.7 4.5 15
009 1
208-230/60/1 197/254 1 5.6 22.2 0.80 6.4 7.8 15
012 1
208-230/60/1 197/254 1 5.1 32.5 0.80 5.9 7.2 15
015
1
208-230/60/1 197/254 1 6.0 29.0 1.00 7.0 8.5 15
8
265/60/1 239/292 1 5.4 28.0 0.86 6.3 7.6 15
018
1
208-230/60/1 197/254 1 7.2 33.0 1.00 8.2 10.0 15
8
265/60/1 239/292 1 5.9 28.0 0.86 6.8 8.2 15
024
1
208-230/60/1 197/254 1 12.8 58.3 1.50 14.3 17.5 30
8
265/60/1 239/292 1 9.6 54.0 1.30 10.9 13.3 20
030
1
208-230/60/1 197/254 1 14.1 73.0 3.00 17.1 20.6 30
8
265/60/1 239/292 1 11.2 60.0 2.70 13.9 16.7 25
3
208-230/60/3 197/254 1 8.9 58.0 3.00 11.9 14.1 20
4
460/60/3 414/506 1 4.2 28.0 1.70 5.9 7.0 15
036
1
208-230/60/1 197/254 1 16.7 79.0 1.80 18.5 22.7 35
8
265/60/1 239/292 1 13.5 72.0 2.00 15.5 18.9 30
3
208-230/60/3 197/254 1 10.4 73.0 1.80 12.2 14.8 25
4
460/60/3 414/506 1 5.8 38.0 1.24 7.0 8.5 15
042
1
208-230/60/1 197/254 1 17.9 112.0 3.00 20.9 25.4 40
3
208-230/60/3 197/254 1 13.5 88.0 3.00 16.5 19.9 30
4
460/60/3 414/506 1 6.0 44.0 1.70 7.7 9.2 15
5
575/60/3 518/633 1 4.9 34.0 1.40 6.3 7.5 15
048
1
208-230/60/1 197/254 1 21.8 117.0 3.40 25.2 30.7 50
3
208-230/60/3 197/254 1 13.7 83.1 3.40 17.1 20.5 30
4
460/60/3 414/506 1 6.2 41.0 1.80 8.0 9.6 15
5
575/60/3 518/633 1 4.8 33.0 1.40 6.2 7.4 15
060
1
208-230/60/1 197/254 1 26.3 134.0 4.90 31.2 37.8 60
3
208-230/60/3 197/254 1 15.6 110.0 4.90 20.5 24.4 40
4
460/60/3 414/506 1 7.8 52.0 2.50 10.3 12.3 20
5
575/60/3 518/633 1 5.8 38.9 1.90 7.7 9.2 15
HACR circuit breaker in USA only
All fuses Class RK-5
29