Heat Controller HBH/V Heat Pump User Manual


 
Engineering Design Guide HBH/V SERIES Heat Controller, Inc.
Blower Performance Data
Standard Unit
Airow in CFM with wet coil and clean air lter
Model
Fan
Speed
Rated
Airow
Min
CFM
Airow (cfm) at External Static Pressure (in. wg)
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
HBH/V 006
HI
220 150
310 300 290 280 270 250 230 210 180
MED 260 250 240 230 210 200 190 150
LOW 210 200 190 180 160 150
HBH/V 009
HI
325 225
410 400 380 360 350 330 320 300 280
MED 390 370 360 340 320 310 290 280 260
LOW 340 330 322 310 300 280 260 250
HBH/V 012
HI
400 300
470 460 450 440 430 420 400 390 380 320
MED 420 410 400 390 380 370 360 350 340
LOW 360 360 350 340 320 320 310 300
HBH/V 015
HI
525 375
745 725 706 696 686 666 637 588 539 451
MED 686 676 666 657 647 637 617 608 588 549 510
LOW 608 598 588 578 568 559 549 529 510 480 451
HBH/V 018
HI
600 450
745 725 706 696 686 666 637 588 539 451
MED 686 676 666 657 647 637 617 608 588 549 510
LOW 608 598 588 578 568 559 549 529 510 480 451
HBH/V 024
HI
800 600
950 922 884 827 732 656
MED 960 950 941 931 912 893 874 855 836 817 789 732 665
LOW 779 770 760 751 741 732 722 713 694 684 665 618
HBH/V 030
HI
1000 750
1102 1074 1045 1017 979 903 798
MED 1188 1169 1140 1121 1093 1064 1036 1017 988 960 922 846
LOW 1064 1045 1017 998 979 960 931 912 884 855 827 751
HBH/V 036
HI
1200 900
1474 1455 1436 1416 1387 1358 1329 1310 1280 1232 1174 1077 931
MED 1174 1164 1106 1106 1096 1096 1086 1077 1067 1038 1009 912
LOW 980 980 970 970 960 960 951 951 941 922 902
HBH/V 042
HI
1350 1050
1558 1530 1501 1473 1444 1416 1378 1340 1302 1264 1226 1131
MED 1416 1397 1368 1349 1321 1302 1273 1245 1207 1169 1131 1064
LOW 1083 1083 1074 1074 1064 1055
HBH/V 048
HI
1600 1200
1881 1853 1815 1767 1710 1653 1596 1416 1216 1216
MED 1843 1824 1805 1786 1767 1729 1682 1653 1625 1577 1520 1340
LOW 1682 1663 1644 1625 1606 1587 1568 1530 1492 1435 1378 1264
HBH/V 060
HI
2000 1500
2195 2195 2185 2176 2156 2117 2078 2048 2019 1999 1970 1921 1842 1754 1627
MED 2009 2009 1999 1980 1950 1931 1901 1882 1852 1823 1793 1744 1676 1588
LOW 1813 1813 1803 1793 1774 1764 1744 1725 1695 1666 1637 1568
Black areas denote ESP where operation is not recommended.
Units factory shipped on medium speed. Other speeds require eld selection.
All airow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
Only two speed fan (H & M) available on 575V units.
Performance stated is at the rated power supply, performance may vary as the power supply varies from the rated.
21