A tap is provided on the outlet side of the gas control for
a test gauge connection to measure the manifold
pressure. To measure inlet pressure, provisions must
be made to attach a test gauge to the tap immediately
upstream of the gas supply connection to the stove.
The stove and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of 60 mbar.
If the stove must be isolated from the gas supply piping
system by closing an individual shut-off valve, it must
be of the handle-less type.
NOTE: Electrical wiring must be installed by a
competent electrician.
For Standing Pilot Ignition Wiring
Appliance Requirements
This appliance DOES NOT require 230 VAC to operate.
WARNING: DO NOT CONNECT 230 VAC
TO THE GAS CONTROL VALVE OR THE
APPLIANCE WILL MALFUNCTION AND
THE VALVE WILL BE DESTROYED.
Optional Accessories
Optional remote control kits require that 230 VAC be
wired to the factory installed junction box before the
fireplace is permanently installed.
Wall Switch
Position the wall switch in the desired position on a
wall. Run a maximum of 7.8 m or less length of 1.02
mm diameter minimum wire and connect it to the
stove ON/OFF switch pigtails.
Step 8
Wiring the
Fireplace
!
Pressure requirements for Heat & Glo gas fireplaces
are shown in the table below.
Step 7
Gas Pressure
Requirements
______________________________________________________________
Natural Gas Propane Butane Natural Gas
(G20) (G31) (G30) (G25)
Inlet Pressure 20mbar 37 or 50mbar 30 or 50mbar 25mbar
Manifold Pressure 4-8.7mbar 15.7-25mbar 15.7-25mbar 4-8.7mbar
Gas Rate .54
m
3
/
h
.24
m
3
/
h
.16
m
3
/
h
.54
m3
/
h
Max.Input(NETCV) 6.0 kW 5.4 kW 5.2kW 5.0 kW
Burner Injector DMS 44 DMS 55 DMS 56 DMS 42
Pilot Injector 51 30 30 51