Hearth and Home Technologies EL42 Indoor Fireplace User Manual


 
42
E. Combustible Mantel
Refer to shaded areas of Figure 11.9 for the location and dimensions of a combustible mantel.
A combustible mantel may be positioned no lower than 12 in. (305 mm) above the top of the replace opening.
A combustible mantel may have a maximum depth of 12 in. (305 mm).
Combustible trim and materials cannot be placed within 6 in. (152mm) of the replace opening (top or sides).
Combustible materials projecting more than 1 1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) from the top of
the replace opening.
Combustible trim must not cover the metal surfaces of the replace.
Mantel clearance is in accordance with Section 7-3.3.3 of ANSI/NFPA211.
7 ft (2134 mm)
minimum
base of fireplace
to ceiling
Combustible Wall
2 x 4 stud wall
Standoffs
Measured from top of fireplace opening
12 in./305 mm
1 1/2 in./38 mm
maximum
12 in./305 mm
minimum
6 in./152 mm
minimum
Combustible
Decorative Facing
Seal joint with
non-combustible
sealant
Non-combustible
Decorative Facing
such as:
Steel, iron, brick,
tile, concrete, slate,
glass, plasters.
Figure 11.9 Clearances to Mantels or other Combustibles above Fireplace
Heatilator • EL36/EL42 • 4044-132 • Rev AD • 7/12