Harman Stove Company TL 300 Stove User Manual


 
11 


The TL300 must be installed into a chimney approved
for use with solid-fuel appliances. In the U.S., the TL300
must be connected to (1) a prefabricated chimney
complying with the requirements for Type HT chimneys
in the Standard for Chimneys, Factory-Built, Residential
Type and Building Heating Appliances, UL 103, or (2)
a code-approved masonry chimney with a ue liner.
In Canada, the TL300 is listed for use with prefabricated
chimneys tested and listed to the high temperature (650
degrees C) chimney standard, ULC S-629, or with a
code approved masonry chimney.
For mobile homes,(US only) the TL300 must only be
installed with prefabricated chimney systems, including
the installation components, tested to use in mobile
homes; the diameter should match the diameter of the
ue collar opening
The minimum recommended height for any chimney
is 16 ft (4.8 m) above ue collar height. For non-mobile
home installations, a round ue (either masonry or
approved prefabricated), of either 6" (150 mm), 7"
(180 mm) or 8" (200 mm) may be used. For square or
rectangular masonry chimneys, nominal sizes of 8" x
8" or 8"x 12" (200mm x 200 mm, 200 mm x 300 mm)
may be used.
Codes require that solid-fuel chimneys extend 3 ft (0.9
m) above the highest point at which they exit from the
roof. Then, the chimney must extend 2 ft.(6 m) above
the highest point within a 10 ft (3 m) radius. Thus, the
3 foot, 2 foot, 10 foot rule:  - Above roof exit point
 - Higher than anything within-
of the chimney.


AN APPROVED CANADIAN WALL
PASS-THROUGH
Hole with a minimum
clearance of 18" (450 mm)
between connector and
wall.
Non-combustible cover,
one side only. If two
covers are used, each
must be mounted on
non-combustible spacers
at least 7/8" (21mm) away
from the wall.
1" (25mm)
Clearance
AN APPROVED U.S.
WALL PASS-THROUGH
Closest
Combusti-
ble Material
Minimum 2" (50mm)
Clearance to Brick
Minimum 12"
(300mm) to Brick
Liner
Fire Clay
Thimble
Chimney
Connector
Chimney Flue
Masonry Chimney Built to
NFPA 211 Specications.
Minimum 12" (300mm)
to Combustibles
: The restriction of not venting more than
one appliance to the same ue applies to the 
specically. While it is not recommended that you
use the same chimney for more than one appliance,
in  certain exceptions may be made. Be sure
to contact your building code inspection ofcial to see
if this option is allowed in your area, and to nd out the
specic requirements for such an installation.
More Than 10 ft. (3m)
10 ft. (3m)
Ridge
Chimney
2 ft. (0.6m) min.
Height Necessary Above
Any Roof Surface Within
10ft. (3m)
3ft. (0.9m)
minimum
above
exit
point
The 3-foot, 2-foot, 10 foot rule