Goodmans GPH 13 H Heat Pump User Manual


 
PACKAGE HEAT PUMP SPECIFICATIONS
26
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.
GPH13[42-60]H41**
EXPANDED PERFORMANCE DATA
MODEL: GPH1348H41** HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 55.953.049.846.644.543.140.136.932.429.927.526.025.022.519.917.414.812.1
DELTA T32.430.628.827.025.825.023.221.418.717.315.915.014.513.011.510.18.6 7.0
KW 3.72 3.65 3.58 3.52 3.48 3.45 3.38 3.32 3.40 3.33 3.26 3.22 3.19 3.12 3.05 2.98 2.90 2.83
AMPS 19.1 17.9 16.9 16.1 15.6 15.4 14.6 14.0 13.5 13.1 12.6 12.3 12.2 11.7 11.1 10.6 10.0 9.3
COP 4.40 4.24 4.07 3.88 3.74 3.66 3.46 3.26 2.79 2.63 2.47 2.37 2.30 2.11 1.91 1.71 1.49 1.25
EER 15.014.513.913.212.812.511.811.19.5 9.0 8.4 8.1 7.9 7.2 6.5 5.8 5.1 4.3
HI PR 366 351 337 323 315 309 297 285 273 261 250 244 240 231 222 213 205 198
LO PR 130 121 113 104 98 94 87 77 70 62 55 51 49 41 36 30 26 21
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1360H41* HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 68.564.961.057.154.552.849.145.239.936.833.932.030.827.624.521.418.214.9
DELTA T34.332.530.628.627.326.424.522.620.018.417.016.015.413.812.310.79.1 7.5
KW 5.30 5.19 5.09 4.98 4.92 4.87 4.77 4.67 41.89 40.71 39.57 38.88 38.42 37.24 36.10 34.96 33.78 32.64
AMPS 22.8 21.3 20.1 19.0 18.4 18.0 17.1 16.3 15.7 15.1 14.5 14.2 14.0 13.4 12.6 12.0 11.2 10.3
COP 3.78 3.65 3.51 3.35 3.24 3.17 3.01 2.84 0.28 0.26 0.25 0.24 0.23 0.22 0.20 0.18 0.16 0.13
EER 12.912.512.011.511.110.810.39.7 1.0 0.9 0.9 0.8 0.8 0.7 0.7 0.6 0.5 0.5
HI PR 370 354 341 326 318 312 300 288 276 263 253 247 242 233 224 215 207 200
LO PR125116108999490837467605249474034292520
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.