Goodmans GPH 13 H Heat Pump User Manual


 
17
COOLING PERFORMANCE DATA GPH1336H41**
MODEL: GPH1336H41**
EXPANDED PERFORMANCE DATA
COOLING OPERATION
Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection.
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 59636771596367715963677159 63 67 715963677159636771
MBh 34.3 35.5 38.9 - 33.5 34.7 38.0 - 32.7 33.9 37.1 - 31.9 33.1 36.2 - 30.3 31.4 34.4 - 28.1 29.1 31.9 -
S/T 0.76 0.63 0.44 - 0.79 0.66 0.45 - 0.81 0.67 0.47 - 0.83 0.69 0.48 - 0.86 0.72 0.50 - 0.87 0.73 0.50 -
Delta T181512 - 181612 - 181612 - 18 16 12 - 181512 - 171411 -
1350 KW 2.61 2.66 2.74 - 2.80 2.85 2.94 - 2.96 3.02 3.12 - 3.11 3.18 3.27 - 3.23 3.30 3.41 - 3.34 3.41 3.52 -
AMPS 11.1 11.3 11.6 - 11.8 12.1 12.4 - 12.7 13.0 13.3 - 13.4 13.7 14.1 - 14.2 14.5 14.9 - 14.9 15.2 15.7 -
HI PR 247 266 281 - 277 298 315 - 315 339 358 - 359 387 408 - 404 435 459 - 446 480 507 -
LO PR 110 117 128 - 116 124 135 - 121 129 140 - 127 135 148 - 133 142 155 - 138 146 160 -
MBh 33.3 34.5 37.8 - 32.5 33.7 36.9 - 31.7 32.9 36.1 - 31.0 32.1 35.2 - 29.4 30.5 33.4 - 27.3 28.3 31.0 -
S/T 0.72 0.60 0.42 - 0.75 0.63 0.43 - 0.77 0.64 0.44 - 0.79 0.66 0.46 - 0.82 0.69 0.48 - 0.83 0.69 0.48 -
Delta T181612 - 191612 - 191612 - 19 16 12 - 191612 - 171511 -
70 1200 KW 2.59 2.64 2.72 - 2.78 2.83 2.92 - 2.94 3.00 3.09 - 3.09 3.15 3.25 - 3.21 3.28 3.38 - 3.32 3.39 3.49 -
AMPS 11.0 11.2 11.5 - 11.8 12.0 12.3 - 12.6 12.9 13.2 - 13.3 13.6 14.0 - 14.1 14.4 14.8 - 14.8 15.1 15.6 -
HI PR 245 263 278 - 275 295 312 - 312 336 355 - 356 383 404 - 400 431 455 - 442 476 502 -
LO PR 109 116 127 - 115 123 134 - 120 127 139 - 126 134 146 - 132 140 153 - 136 145 158 -
MBh 30.7 31.9 34.9 - 30.0 31.1 34.1 - 29.3 30.4 33.3 - 28.6 29.6 32.5 - 27.2 28.2 30.8 - 25.2 26.1 28.6 -
S/T 0.70 0.58 0.40 - 0.72 0.60 0.42 - 0.74 0.62 0.43 - 0.76 0.64 0.44 - 0.79 0.66 0.46 - 0.80 0.67 0.46 -
Delta T191612 - 191612 - 191612 - 19 17 13 - 191612 - 181512 -
1050 KW 2.53 2.58 2.66 - 2.71 2.77 2.85 - 2.87 2.93 3.02 - 3.01 3.08 3.17 - 3.13 3.20 3.30 - 3.24 3.30 3.41 -
AMPS 10.8 11.0 11.3 - 11.5 11.7 12.0 - 12.3 12.6 12.9 - 13.0 13.3 13.7 - 13.7 14.0 14.4 - 14.4 14.8 15.2 -
HI PR 237 255 270 - 266 287 303 - 303 326 344 - 345 371 392 - 388 418 441 - 429 461 487 -
LO PR 106 113 123 - 112 119 130 - 116 124 135 - 122 130 142 - 128 136 148 - 132 141 154 -
MBh 34.935.938.941.734.135.138.040.733.334.237.139.832.4
33.4
36.2 38.8 30.8 31.7 34.4 36.9 28.6 29.4 31.8 34.2
S/T 0.860.770.580.380.890.800.600.390.920.820.620.400.94
0.85
0.64 0.41 0.98 0.88 0.66 0.43 0.99 0.88 0.67 0.43
Delta T20191511211916112119161121
19
16 11 21 19 16 11 19 18 15 10
1350 KW 2.63 2.68 2.76 2.84 2.82 2.88 2.96 3.06 2.99 3.05 3.14 3.24 3.13
3.20
3.30 3.41 3.26 3.33 3.44 3.55 3.37 3.44 3.55 3.67
AMPS 11.2 11.4 11.7 12.1 11.9 12.2 12.5 12.9 12.8 13.1 13.4 13.9 13.6
13.8
14.2 14.7 14.3 14.6 15.0 15.5 15.0 15.4 15.8 16.4
HI PR 250 269 284 296 280 301 318 332 319 343 362 378 363
391
412 430 408 439 464 484 451 485 513 535
LO PR 111 118 129 138 118 125 137 145 122 130 142 151 128
137
149 159 134 143 156 166 139 148 162 172
MBh 33.934.937.740.533.134.136.939.632.333.236.038.631.5
32.4
35.1 37.7 29.9 30.8 33.3 35.8 27.7 28.5 30.9 33.2
S/T 0.820.730.560.360.850.760.580.370.870.780.590.380.90
0.81
0.61 0.39 0.94 0.84 0.63 0.41 0.94 0.84 0.64 0.41
Delta T21201611222016112220161122
20
16 11 21 20 16 11 20 18 15 10
75 1200 KW 2.61 2.66 2.74 2.82 2.80 2.85 2.94 3.03 2.96 3.02 3.12 3.22 3.11
3.18
3.27 3.38 3.23 3.30 3.41 3.52 3.34 3.41 3.52 3.64
AMPS 11.1 11.3 11.6 12.0 11.8 12.1 12.4 12.8 12.7 13.0 13.3 13.8 13.4
13.7
14.1 14.6 14.2 14.5 14.9 15.4 14.9 15.2 15.7 16.2
HI PR 247 266 281 293 277 298 315 329 315 339 358 374 359
387
408 426 404 435 459 479 447 481 507 529
LO PR 110 117 128 136 116 124 135 144 121 129 140 150 127
135
148 157 133 142 155 165 138 147 160 170
MBh 31.332.234.837.430.531.434.036.529.830.733.235.629.1
29.9
32.4 34.8 27.6 28.4 30.8 33.0 25.6 26.3 28.5 30.6
S/T 0.790.710.540.340.820.730.560.360.840.750.570.370.87
0.78
0.59 0.38 0.90 0.81 0.61 0.39 0.91 0.81 0.62 0.40
Delta T22201611222017112220171122
20
17 12 22 20 16 11 20 19 15 11
1050 KW 2.55 2.60 2.68 2.76 2.73 2.79 2.87 2.96 2.89 2.95 3.04 3.14 3.04
3.10
3.20 3.30 3.16 3.22 3.33 3.43 3.26 3.33 3.44 3.55
AMPS 10.9 11.1 11.4 11.7 11.6 11.8 12.1 12.5 12.4 12.7 13.0 13.4 13.1
13.4
13.8 14.2 13.9 14.1 14.6 15.0 14.6 14.9 15.3 15.8
HI PR 240 258 272 284 269 290 306 319 306 329 348 363 349
375
396 413 392 422 446 465 433 466 492 513
LO PR 107 114 124 132 113 120 131 140 117 125 136 145 123
131
143 152 129 137 150 160 134 142 155 165
* Entering Indoor Dry Bulb Temperature NOTE: Shaded area is ACCA (TVA) conditions
High and low pressures are measured at the liquid and suction access fittings.