Goodmans GPH 13 H Heat Pump User Manual


 
15
COOLING PERFORMANCE DATA GPH1330H41**
MODEL: GPH1330H41**
EXPANDED PERFORMANCE DATA
COOLING OPERATION
Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection.
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 59636771596367715963677159 63 67 715963677159636771
MBh 27.6 28.6 31.4 - 27.0 28.0 30.7 - 26.3 27.3 29.9 - 25.7 26.6 29.2 - 24.4 25.3 27.7 - 22.6 23.4 25.7 -
S/T 0.80 0.67 0.46 - 0.83 0.69 0.48 - 0.85 0.71 0.49 - 0.87 0.73 0.51 - 0.91 0.76 0.52 - 0.91 0.76 0.53 -
Delta T171511 - 171511 - 171511 - 18 15 11 - 171511 - 161411 -
1180 KW 2.03 2.07 2.13 - 2.18 2.22 2.29 - 2.31 2.36 2.43 - 2.43 2.48 2.56 - 2.53 2.58 2.66 - 2.61 2.67 2.75 -
AMPS 8.7 8.8 9.1 - 9.3 9.4 9.7 - 9.9 10.1 10.4 - 10.5 10.8 11.1 - 11.1 11.4 11.7 - 11.7 12.0 12.3 -
HI PR 247 265 280 - 277 298 314 - 315 339 358 - 358 386 407 - 403 434 458 - 446 479 506 -
LO PR 112 119 130 - 118 126 137 - 123 131 143 - 129 137 150 - 135 144 157 - 140 149 162 -
MBh 26.8 27.8 30.5 - 26.2 27.2 29.8 - 25.6 26.5 29.0 - 25.0 25.9 28.3 - 23.7 24.6 26.9 - 22.0 22.8 24.9 -
S/T 0.76 0.63 0.44 - 0.79 0.66 0.46 - 0.81 0.67 0.47 - 0.83 0.70 0.48 - 0.87 0.72 0.50 - 0.87 0.73 0.50 -
Delta T181512 - 181612 - 181612 - 18 16 12 - 181612 - 171511 -
70 1050 KW 2.01 2.05 2.12 - 2.16 2.21 2.27 - 2.29 2.34 2.41 - 2.41 2.46 2.54 - 2.51 2.56 2.64 - 2.59 2.65 2.73 -
AMPS 8.6 8.8 9.0 - 9.2 9.4 9.6 - 9.9 10.1 10.4 - 10.4 10.7 11.0 - 11.0 11.3 11.6 - 11.6 11.9 12.2 -
HI PR 244 263 277 - 274 295 311 - 312 335 354 - 355 382 403 - 399 430 454 - 441 475 501 -
LO PR 111 118 129 - 117 124 136 - 121 129 141 - 128 136 148 - 134 142 155 - 138 147 161 -
MBh 24.8 25.7 28.1 - 24.2 25.1 27.5 - 23.6 24.5 26.8 - 23.0 23.9 26.2 - 21.9 22.7 24.9 - 20.3 21.0 23.0 -
S/T 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.78 0.65 0.45 - 0.80 0.67 0.47 - 0.83 0.70 0.48 - 0.84 0.70 0.49 -
Delta T181612 - 181612 - 181612 - 18 16 12 - 181612 - 171511 -
920 KW 1.97 2.01 2.07 - 2.11 2.15 2.22 - 2.24 2.28 2.36 - 2.35 2.40 2.48 - 2.45 2.50 2.58 - 2.53 2.58 2.66 -
AMPS 8.4 8.6 8.8 - 9.0 9.1 9.4 - 9.6 9.8 10.1 - 10.2 10.4 10.7 - 10.8 11.0 11.3 - 11.3 11.6 11.9 -
HI PR 237 255 269 - 266 286 302 - 302 325 343 - 344 370 391 - 387 417 440 - 428 460 486 -
LO PR 107 114 125 - 113 121 132 - 118 125 137 - 124 132 144 - 130 138 151 - 134 143 156 -
MBh 28.1 28.9 31.3 33.6 27.4 28.3 30.6 32.8 26.8 27.6 29.9 32.0 26.1
26.9
29.1 31.3 24.8 25.6 27.7 29.7 23.0 23.7 25.6 27.5
S/T 0.910.810.610.390.940.840.640.410.960.860.650.420.99
0.89
0.67 0.43 1.00 0.92 0.70 0.45 1.00 0.93 0.70 0.45
Delta T20181510201815102019151020
19
15 11 19 18 15 10 18 17 14 10
1180 KW 2.04 2.09 2.15 2.22 2.20 2.24 2.31 2.38 2.33 2.38 2.45 2.53 2.45
2.50
2.58 2.66 2.55 2.60 2.69 2.77 2.63 2.69 2.78 2.87
AMPS 8.7 8.9 9.1 9.4 9.3 9.5 9.8 10.1 10.0 10.2 10.5 10.9 10.6
10.8
11.2 11.5 11.2 11.5 11.8 12.2 11.8 12.1 12.4 12.9
HI PR 249 268 283 295 280 301 318 331 318 342 361 377 362
390
411 429 407 438 463 483 450 484 511 533
LO PR 113 120 131 140 119 127 139 148 124 132 144 153 130
139
151 161 136 145 158 169 141 150 164 175
MBh 27.3 28.1 30.4 32.6 26.6 27.4 29.7 31.9 26.0 26.8 29.0 31.1 25.4
26.1
28.3 30.4 24.1 24.8 26.9 28.8 22.3 23.0 24.9 26.7
S/T 0.860.770.580.380.900.800.610.390.920.820.620.400.95
0.85
0.64 0.41 0.98 0.88 0.67 0.43 0.99 0.89 0.67 0.43
Delta T21191611211916112119161121
19
16 11 21 19 16 11 19 18 15 10
75 1050 KW 2.03 2.07 2.13 2.20 2.18 2.22 2.29 2.36 2.31 2.36 2.43 2.51 2.43
2.48
2.56 2.64 2.53 2.58 2.66 2.75 2.61 2.67 2.76 2.85
AMPS 8.7 8.8 9.1 9.4 9.3 9.4 9.7 10.0 9.9 10.1 10.4 10.8 10.5
10.8
11.1 11.4 11.1 11.4 11.7 12.1 11.7 12.0 12.3 12.7
HI PR 247 265 280 292 277 298 315 328 315 339 358 373 358
386
407 425 403 434 458 478 446 480 506 528
LO PR 112 119 130 138 118 126 137 146 123 131 143 152 129
137
150 159 135 144 157 167 140 149 162 173
MBh 25.2 25.9 28.1 30.1 24.6 25.3 27.4 29.4 24.0 24.7 26.8 28.7 23.4
24.1
26.1 28.0 22.3 22.9 24.8 26.6 20.6 21.2 23.0 24.7
S/T 0.830.740.560.360.860.770.580.380.890.790.600.390.91
0.82
0.62 0.40 0.95 0.85 0.64 0.41 0.96 0.86 0.65 0.42
Delta T21191611212016112120161121
20
16 11 21 19 16 11 20 18 15 10
920 KW 1.982.022.082.152.132.172.242.312.262.302.372.452.37
2.42
2.50 2.58 2.47 2.52 2.60 2.68 2.55 2.60 2.69 2.78
AMPS 8.5 8.6 8.9 9.1 9.0 9.2 9.5 9.8 9.7 9.9 10.2 10.5 10.3
10.5
10.8 11.2 10.9 11.1 11.4 11.8 11.4 11.7 12.0 12.4
HI PR 239 257 272 284 268 289 305 318 305 329 347 362 348
374
395 412 391 421 445 464 432 465 491 512
LO PR 108 115 126 134 115 122 133 142 119 127 138 147 125
133
145 155 131 139 152 162 136 144 157 168
* Entering Indoor Dry Bulb Temperature NOTE: Shaded area is ACCA (TVA) conditions
High and low pressures are measured at the liquid and suction access fittings.