Goodman Mfg SS-DSZC18 Air Conditioner User Manual


 
produCt SpeCifiCationS
produCt SpeCifiCationS
SS-DSZC18 www.goodmanmfg.com 3
SpeCifiCationS
DSZC18
0361A
DSZC18
0481A
DSZC18
0601A
DSZC18
0601B
Cooling Capacity
Nominal Cooling (BTU/h) 35,000 47,000 57,000 57,000
Nominal Heang (BTU/h) 35,000 47,000 57,000 57,000
Decibels 72 73 75 75
Compressor
RLA 16.7 21.2 25.6 23.0
LRA 82 96 118 118
Condenser Fan Motor
Horsepower (RPM)
FLA 2.8 2.8 2.8 2.8

Refrigerant Line Size¹
Liquid Line Size (“O.D.) ⅜" ⅜" ⅜" ⅜"
Sucon Line Size (“O.D.) ⅞" 1⅛" 1⅛" 1⅛"
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) ⅜" ⅜" ⅜" ⅜"
Sucon Valve Size (“O.D.) ⅞" 1⅛" 1⅛" 1⅛"
Valve Connecon Type Sweat Sweat Sweat Sweat
Refrigerant Charge 188 278 278 278
Expansion Device TXV TXV TXV TXV
Superheat at Service Valve 7-9°F 7-9°F 7-9°F 7-9°F
Subcooling at Service Valve
High Stage 8-10°F 8-10°F 8-10°F 8-10°F
Low Stage 5-7°F 5-7°F 5-7°F 5-7°F
Electrical Data
Voltage-Phase-Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Minimum Circuit Ampacity ² 23.7 29.3 34.8 31.6
Max. Overcurrent Protecon ³ 40 50 60 50
Min / Max Volts 197 / 253 197 / 253 197 / 253 197 / 253
Electrical Conduit Size ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾"
Ship Weight (lbs) 293 340 360 360
¹ Tested and rated in accordance with ARI Standard 210/240
² Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.

Always check the rang plate for electrical data on the unit being installed.
Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installaon Instrucons Final Charge Procedure.
Installaon of these units requires the specied TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT,
NOT THE INDOOR COIL.