Goodman Mfg SS-CPG180-240 Air Conditioner User Manual


 
prodUCT speCifiCaTions
prodUCT speCifiCaTions
6 www.goodmanmfg.com SS-CPG180-240
airflow daTa 15 Tons




0 1 2 3 4 5 6
 BHP  BHP  BHP  BHP  BHP  BHP  BHP
0.2 0.00 6827 2.67 6394 2.28 5982 1.94
0.4 7079 3.20 6623 2.76 6161 2.34 5706 1.98 5271 1.66
0.6 6903 3.32 6405 2.83 5923 2.41 5434 2.02 4949 1.68
0.8 6717 3.42 6198 2.92 5668 2.45 5152 2.05
1.0 5975 2.99 5418 2.51
1.2 5147 2.55




0 1 2 3 4 5 6
 BHP  BHP  BHP  BHP  BHP  BHP  BHP
1.0 6690 3.69 6008 3.02 5321 2.43
1.2 6653 3.95 5922 3.22 5182 2.58
1.4 6634 2.80 5857 3.44 5056 2.74
1.6 6638 4.55 5808 2.43 4948 2.91
1.8 6683 4.93 5784 3.95 4855 2.05
2.0 5803 4.27 4788 3.32

Airow table represent dry coil with lters installed; SCFM correcon factor for wet coil is 4%.
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applicaon that exceed the above could
require a larger motor. Minimum rated SCFM is 350 per ton.
High-stac airow requires installaon of high kit (HSKT180G) or factory-built high-stac model.
Unit factory shipped with the sheave set at 2.5 turns open.