Goodman Mfg SS-CPG180-240 Air Conditioner User Manual


 
prodUCT speCifiCaTions
prodUCT speCifiCaTions
SS-CPG180-240 www.goodmanmfg.com 5
prodUCT speCifiCaTions 20 Tons
CPG240
4003B***
CPG240
4004B***
CPG240
4007B***

Total, BTU/h 240,000 240,000 240,000
Sensible BTU/h 170,000 170,000 170,000
EER / IEER 9.8 / 10.0 9.8 / 10.0 9.8 / 10.0
Decibels 88.3 88.3 88.3
AHRI Reference #s 3897346 3897346 3897346

Max. Input High / Low (KBTU/h) 400 / 300 400 / 300 400 / 300
Output BTU/h 320 / 240 320 / 240 320 / 240
Steady State Eciency (%) 80 80 80
Temperature Rise Range (°F) High/Low 25-55 / 15-45 25-55 / 15-45 25-55 / 15-45
No. of Burners 8 8 8

Motor Type (Belt Drive) Std Stac Belt Drive Std Stac Belt Drive Std Stac Belt Drive
Indoor Nominal CFM 7,000 7,000 7,000
Indoor Motor FLA (Cooling) 12.7 6.4 5.1
Horsepower - RPM 5.0 - 1,725 5.0 - 1,725 5.0 - 1,725
Metering Device TXV TXV TXV
Filter Size (#) 25 x 25 x 2 (6) 25 x 25 x 2 (6) 25 x 25 x 2 (6)
Drain Size (NPT) 1" 1" 1"
R-410A Refrigerant Charge Cir #s 1 & 2 320 oz. 320 oz. 320 oz.
Evaporator Coil Face Area (²) 20 20 20
Rows Deep / Fins per Inch 4 / 16 4 / 16 4 / 16

# of Wheels (D x W) 2 (15" x 15") 2 (15" x 15") 2 (15" x 15")
Motor Sheave 1VP60 x 1⅛" 1VP60 x 1⅛" 1VP60 x 1⅛"
Blower Sheave / Belt BK100 x 1⁷/₁₆" / BX46 BK100 x 1⁷/₁₆" / BX46 BK100 x 1⁷/₁₆" / BX46

Quanty of Condenser Fan Motors 3 3 3
Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075
Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 3
Outdoor Nominal CFM 7,200 7,200 7,200
Face Area (²) 53.3 53.3 53.3
Rows Deep / Fins per Inch 2 / 18 2 / 18 2 / 18

Quanty / Type 2 / Scroll 2 / Scroll 2 / Scroll
Compressor RLA / LRA ea. 33.3 / 239 17.9 / 125 12.8 / 80

Voltage / Phase / Frequency 208-230/3/60 460/3/60 575/3/60
Standard Max Stac 1.4 1.4 1.4
Outdoor Fan FLA / LRA 2.4 / 5.2 1.2 / 2.6 .9 / 2.2
Total Unit Amps 86.5 45.8 33.4
Min. Circuit Ampacity¹ 95 50 37
Max. Overcurrent Protecon (amps)² 125 60 45
Entrance Power Supply 2⅛" 2⅛" 2⅛"
Entrance Control Voltage ⅞" ⅞" ⅞"
 2275 2275 2275
 2390 2390 2390
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.