Goodman Mfg SS-CPG180-240 Air Conditioner User Manual


 
prodUCT speCifiCaTions
prodUCT speCifiCaTions
4 www.goodmanmfg.com SS-CPG180-240
prodUCT speCifiCaTions 15 Tons
CPG180350
3B***
CPG180350
4B***
CPG180***
7B***

Total, BTU/h 180,000 180,000 180,000
Sensible BTU/h 127,500 127,500 127,500
EER / IEER 10.8 / 11 10.8 / 11 10.8 / 11
Decibels 88 88 88
ARI Reference #s 3965698 3965698 3965698

Max. Input: High / Low KBTU/h 350 / 262 350 / 262 350 / 262
Output: High / Low KBTU/h 280 / 210 280 / 210 280 / 210
Steady State Eciency (%) 80 80 80
Temperature Rise: High / Low (°F) 30-60 / 20-50 30-60 / 20-50 30-60 / 20-50
No. of Burners 7 7 7

Motor Type (Belt Drive) Std Stac Std Stac Std Stac
Indoor Nominal CFM 5,400 5,400 5,400
Indoor Motor FLA (Cooling) 12.7 6.4 5.1
Horsepower - RPM 5.0 - 1,725 5.0 - 1,725 5.0 - 1,725
Metering Device TXV TXV TXV
Filter Size (#) 20 x 25 x 2 (6) 20 x 25 x 2 (6) 20 x 25 x 2 (6)
Drain Size (NPT) 1" 1" 1"
R-410A Refrigerant Charge Cir #1 & 2 290 oz. 290 oz. 290 oz.
Evaporator Coil Face Area (²) 20 20 20
Rows Deep / Fins per Inch 4 / 16 4 / 16 4 / 16

# of Wheels (D x W) 2 (15" x 12") 2 (15" x 12") 2 (15" x 12")
Motor Sheave 1VP50 x 1⅛" 1VP50 x 1⅛" 1VP50 x 1⅛"
Blower Sheave / Belt BK90 x 1³/₁₆" / BX42 BK90 x 1³/₁₆" / BX42 BK90 x 1³/₁₆" / BX42

Quanty of Condenser Fan Motors 3 3 3
Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075
Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 3
Outdoor Nominal CFM 7,200 7,200 7,200
Face Area (²) 53.3 53.3 53.3
Rows Deep / Fins per Inch 2 / 18 2 / 18 2 / 18

Quanty / Type 2 / Scroll 2 / Scroll 2 / Scroll
Compressor RLA / LRA CIR. #1 25 / 164 12.2 / 100 9.0 / 78
Compressor RLA / LRA CIR. #2 29.5 / 195 14.7 / 95 12.2 / 80

Voltage / Phase / Frequency 208-230/3/60 460/3/60 575/3/60
Standard Max Stac 1.2 1.2 1.2
Outdoor Fan FLA / LRA 2.4 / 5.2 1.2 / 2.6 .9 / 2.2
Total Unit Amps 74.4 36.9 29
Min. Circuit Ampacity¹ 81.8 40.6 32.1
Max. Overcurrent Protecon (amps)² 100 50 40
Entrance Power Supply 2⅛" 2⅛" 2⅛"
Entrance Control Voltage ⅞" ⅞" ⅞"
 2155 2155 2155
 2270 2270 2270
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.